NSN 5925-00-945-5463 · NIIN 009455463 · FSC 5925
NO DASHES 5925009455463
In Stock
CIRCUIT BREAKER
Circuit Breakers
Technical characteristics
30 rows
Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.
| MRC | Requirement | Value |
|---|---|---|
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | THREADED BUSHING 1 |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | TOGGLE 1 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | SINGLE LOCATION AMPERES AC 1.5 AND AMPERES DC 1.5 |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 115.0 |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | SINGLE LOCATION AC 240.0 AND DC 50.0 |
| THSD | THREAD SERIES DESIGNATOR | UNEF |
| TTQY | TERMINAL TYPE AND QUANTITY | WIRE HOOK 2 |
| CPRL | TRIP RELEASE CHARACTERISTIC | SINGLE LOCATION TIME DELAY |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SINGLE LOCATION SERIES TRIP |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | SINGLE LOCATION AC 1000.0 AND DC 1000.0 |
| AAJE | THREAD PITCH DIAMETERS | INCHES 0.3503 TO 0.3537 |
| AAQL | BODY STYLE | |
| ABXD | BUSHING LENGTH | INCHES MAXIMUM 0.380 |
| ADAQ | BODY LENGTH | INCHES MAXIMUM 1.500 |
| ADAT | BODY WIDTH | INCHES MAXIMUM 0.625 |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | INCHES NOMINAL 0.875 |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | INCHES MAXIMUM 1.605 |
| AKPX | POLE QUANTITY | 1 |
| FREQ | FREQUENCY IN HERTZ | 400.0 |
| CPRJ | TRIP RELEASE METHOD | SINGLE LOCATION MAGNETIC |
| CQJX | NOMINAL THREAD SIZE | INCHES 0.375 |
| CMLP | THREAD QUANTITY PER INCH | 32 |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | SHOCKPROOF AND VIBRATIONPROOF AND HERMETICALLY SEALED |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRH | CIRCUIT PROTECTION TYPE | SINGLE LOCATION OVERCURRENT |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | SINGLE LOCATION MINIMUM AT 200 PCT 0.120 AND MAXIMUM AT 200 PCT 0.600 |
| CPRQ | RESET METHOD | MANUAL |
Supersedes
This item replaces cancelled NIIN 007271439. An older drawing citing one of those numbers resolves here.