CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

33 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
FREQFREQUENCY IN HERTZ400.0
THSDTHREAD SERIES DESIGNATORUNS
TTQYTERMINAL TYPE AND QUANTITYSCREW 6
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 208.0
MATTMATERIALCASE PLASTIC
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 0.280 AND MAXIMUM AT 200 PCT 0.900
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDEXPLOSION RESISTANT
CQJXNOMINAL THREAD SIZEINCHES 0.138
AAQLBODY STYLE
ADAQBODY LENGTHINCHES NOMINAL 2.500
ADATBODY WIDTHINCHES NOMINAL 2.273
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 1.190
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 0.750
CPRYEXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED
CPSMINTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 3
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONAT EACH POLE
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT150.0
CPRPULTIMATE TRIP TIME PER POLE IN SECONDSALL LOCATIONS MINIMUM 1.000 AND MAXIMUM 4.000
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 6
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 3500.0
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES NOMINAL 2.000
CMLPTHREAD QUANTITY PER INCH32
CPRJTRIP RELEASE METHODALL LOCATIONS MAGNETIC-HYDRAULIC
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES NOMINAL 1.812
AEHADISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES NOMINAL 0.750
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 40.0
AKPXPOLE QUANTITY3