Home / MS parts / NSN 5925-00-850-8145
NSN 5925-00-850-8145  ·  NIIN 008508145  ·  FSC 5925
NO DASHES 5925008508145
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

35 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
TTQYTERMINAL TYPE AND QUANTITYSCREW 2
THSDTHREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
CPSMINTERNAL TRIP RELEASE CONFIGURATIONSINGLE LOCATION SERIES TRIP
CQJXNOMINAL THREAD SIZEINCHES 0.138
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTSINGLE LOCATION MINIMUM AT 200 PCT 0.400 AND MAXIMUM AT 200 PCT 1.200
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLESINGLE LOCATION AMPERES AC 5.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSSINGLE LOCATION AC 208.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSSINGLE LOCATION AC 3500.0
CPRHCIRCUIT PROTECTION TYPESINGLE LOCATION OVERCURRENT
AKPXPOLE QUANTITY1
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
TESTTEST DATA DOCUMENTDRAWING (THIS IS THE BASIC GOVERNING DRAWING, SUCH AS A CONTRACTOR DRAWING, ORIGINAL EQUIPMENT MANUFACTURER DRAWING, ETC.; EXCLUDES ANY SPECIFICATION, STANDARD OR OTHER DOCUMENT THAT MAY BE REFERENCED IN A BASIC GOVERNING DRAWING) 08440-150-0762
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDEXPLOSION RESISTANT
CTJSUNPACKAGED UNIT WEIGHTOUNCES NOMINAL 4.225
FREQFREQUENCY IN HERTZ60.0
MATTMATERIALCASE PLASTIC
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT150.0
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 2
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
BBRJSPECIAL HANDLING FEATUREMAGNETIC
CMLPTHREAD QUANTITY PER INCH32
AAQLBODY STYLE
ADAQBODY LENGTHINCHES NOMINAL 2.500
ADATBODY WIDTHINCHES NOMINAL 0.750
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 1.190
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES NOMINAL 1.812
AFJNFRAGILITY FACTORMODERATELY RUGGED
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES NOMINAL 2.000
CPRQRESET METHODMANUAL
CPRJTRIP RELEASE METHODSINGLE LOCATION MAGNETIC-HYDRAULIC
CPRLTRIP RELEASE CHARACTERISTICSINGLE LOCATION TIME DELAY
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONAT POLE ONE