Home / MS parts / NSN 5925-01-249-9062
NSN 5925-01-249-9062  ·  NIIN 012499062  ·  FSC 5925
NO DASHES 5925012499062
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

39 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
AAQLBODY STYLE
ADAQBODY LENGTHINCHES NOMINAL 16.000
ADATBODY WIDTHINCHES NOMINAL 8.250
ADAUBODY HEIGHTINCHES NOMINAL 4.062
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 11.500
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 2.750
AEBVUNTHREADED MOUNTING HOLE DIAMETERINCHES NOMINAL 0.344
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES NOMINAL 14.375
AEHADISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES NOMINAL 2.750
AFJNFRAGILITY FACTORMODERATELY RUGGED
AJECBOSS HEIGHTINCHES NOMINAL 0.938
AKPXPOLE QUANTITY3
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
AXHRMOUNTING FACILITY TYPE AND QUANTITYUNTHREADED HOLE(S) 4
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
BBRJSPECIAL HANDLING FEATUREMAGNETIC
CBBLFEATURES PROVIDEDADJUSTABLE TRIP RELEASE AND INTERCHANGEABLE TRIP RELEASE
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 800.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 600.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 22000.0
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
CPRJTRIP RELEASE METHODALL LOCATIONS MAGNETIC
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS INSTANTANEOUS AND TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONAT POLE TWO
CPSFADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPSALL LOCATIONS AC 4000.0 TO 8000.0
CPSMINTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 2.000 AND MAXIMUM AT 200 PCT 45.000
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDCORROSION RESISTANT AND FUNGUS RESISTANT AND SHOCK RESISTANT AND VIBRATION RESISTANT
FEATSPECIAL FEATURESINCLUDES FLUX TRANSFER SHUNT TRIP,RATED 32 VDC,120 VAC,60 HZ
FREQFREQUENCY IN HERTZ63.0
MATTMATERIALCASE PLASTIC
PMLCPRECIOUS MATERIAL AND LOCATIONSILVER CONTACTS
PRMTPRECIOUS MATERIALSILVER
TTQYTERMINAL TYPE AND QUANTITYCOMPRESSION 6

Supersedes