Home / MS parts / NSN 5925-00-681-6077
NSN 5925-00-681-6077  ·  NIIN 006816077  ·  FSC 5925
NO DASHES 5925006816077
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

33 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDDUSTPROOF
MATTMATERIALCASE PLASTIC
TTQYTERMINAL TYPE AND QUANTITYCOMPRESSION 6
APNQARC QUENCHING METHODDEION
AXHRMOUNTING FACILITY TYPE AND QUANTITYUNTHREADED HOLE(S) 4
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
BBRJSPECIAL HANDLING FEATUREMAGNETIC
CRCFTRIP RELEASE AMBIENT TEMP RATINGALL LOCATIONS CELSIUS NOMINAL 40.0
FREQFREQUENCY IN HERTZ60.0
ADAQBODY LENGTHINCHES MINIMUM 9.370 AND INCHES MAXIMUM 9.380
ADATBODY WIDTHINCHES MINIMUM 4.120 AND INCHES MAXIMUM 4.130
ADAUBODY HEIGHTINCHES MINIMUM 3.807 AND INCHES MAXIMUM 3.817
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES MINIMUM 7.245 AND INCHES MAXIMUM 7.255
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES MINIMUM 1.369 AND INCHES MAXIMUM 1.379
AEBVUNTHREADED MOUNTING HOLE DIAMETERINCHES NOMINAL 0.281
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES MINIMUM 4.495 AND INCHES MAXIMUM 4.505
CPRXACTUATOR POSITION DESIGNATIONAT POLE TWO
AAQLBODY STYLE
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRJTRIP RELEASE METHODALL LOCATIONS THERMAL-MAGNETIC
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS INSTANTANEOUS
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
CPRQRESET METHODMANUAL
AFJNFRAGILITY FACTORMODERATELY RUGGED
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 90.0 AND AMPERES DC 90.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 600.0 AND DC 250.0
AJECBOSS HEIGHTINCHES MINIMUM 0.120 AND INCHES MAXIMUM 0.130
AKPXPOLE QUANTITY3
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 15000.0 AND DC 10000.0
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
AEHADISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES MINIMUM 1.369 AND INCHES MAXIMUM 1.379

Supersedes