Home / MS parts / NSN 5925-00-227-0386
NSN 5925-00-227-0386  ·  NIIN 002270386  ·  FSC 5925
NO DASHES 5925002270386
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

23 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
AKPXPOLE QUANTITY1
CMLPTHREAD QUANTITY PER INCH32
AEBVUNTHREADED MOUNTING HOLE DIAMETERINCHES NOMINAL 0.188
CPRPULTIMATE TRIP TIME PER POLE IN SECONDSSINGLE LOCATION MINIMUM 80.000 AND MAXIMUM 3600.000
AXHRMOUNTING FACILITY TYPE AND QUANTITYUNTHREADED HOLE(S) 2
THSDTHREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
TTQYTERMINAL TYPE AND QUANTITYTHREADED STUD 2
CPRWACTUATOR FUNCTIONTRIP W/SEPARATE RESET
CPSMINTERNAL TRIP RELEASE CONFIGURATIONSINGLE LOCATION SERIES TRIP
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLESINGLE LOCATION AMPERES AC 25.0 AND AMPERES DC 25.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSSINGLE LOCATION AC 120.0 AND DC 32.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSSINGLE LOCATION AC 5000.0 AND DC 5000.0
CPRLTRIP RELEASE CHARACTERISTICSINGLE LOCATION TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
CQJXNOMINAL THREAD SIZEINCHES 0.164
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTSINGLE LOCATION MINIMUM AT 200 PCT 12.800 AND MAXIMUM AT 200 PCT 38.000
CRCFTRIP RELEASE AMBIENT TEMP RATINGSINGLE LOCATION CELSIUS NOMINAL 25.0
CPRJTRIP RELEASE METHODSINGLE LOCATION THERMAL
CPRHCIRCUIT PROTECTION TYPESINGLE LOCATION OVERCURRENT
MATTMATERIALCASE PLASTIC
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1

Supersedes

This item replaces cancelled NIINs 001752662 · 002801324 · 007665116. An older drawing citing one of those numbers resolves here.