NSN 5925-00-318-0026 · NIIN 003180026 · FSC 5925
NO DASHES 5925003180026
In Stock
CIRCUIT BREAKER
Circuit Breakers
Technical characteristics
40 rows
Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.
| MRC | Requirement | Value |
|---|---|---|
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | THREADED HOLE(S) 4 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | ALL LOCATIONS AMPERES AC 3.0 |
| ADAQ | BODY LENGTH | INCHES MAXIMUM 2.510 |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | INCHES MINIMUM 2.046 AND INCHES MAXIMUM 2.078 |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | INCHES MAXIMUM 2.553 |
| ADAT | BODY WIDTH | INCHES NOMINAL 1.500 |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | INCHES MINIMUM 1.660 AND INCHES MAXIMUM 1.960 |
| CPRL | TRIP RELEASE CHARACTERISTIC | ALL LOCATIONS TIME DELAY |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 115.0 |
| CPRQ | RESET METHOD | MANUAL |
| AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | INCHES NOMINAL 0.750 |
| CPRH | CIRCUIT PROTECTION TYPE | ALL LOCATIONS OVERCURRENT |
| CPRJ | TRIP RELEASE METHOD | ALL LOCATIONS MAGNETIC |
| AKPX | POLE QUANTITY | 2 |
| APNQ | ARC QUENCHING METHOD | MAGNETIC BLOWOUT |
| CMLP | THREAD QUANTITY PER INCH | 32 |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | TOGGLE 2 |
| AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | INCHES NOMINAL 0.750 |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
| AAJE | THREAD PITCH DIAMETERS | INCHES 0.1177 TO 0.1214 |
| AAQL | BODY STYLE | |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND MOISTURE RESISTANT AND SALT SPRAY PROOF AND SHOCK RESISTANT AND VIBRATION RESISTANT |
| ZZZK | SPECIFICATION/STANDARD DATA | GOVERNMENT SPECIFICATION 81349--IL-C-55629 TO 3 |
| CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
| CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | ALL LOCATIONS SERIES TRIP |
| CQJX | NOMINAL THREAD SIZE | INCHES 0.138 |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | ALL LOCATIONS MINIMUM AT 200 PCT 2.200 AND MAXIMUM AT 200 PCT 20.000 |
| FREQ | FREQUENCY IN HERTZ | 60.0 |
| MATT | MATERIAL | CASE PLASTIC |
| TEST | TEST DATA DOCUMENT | SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.). 81349--IL-C-55629 |
| THSD | THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| TTQY | TERMINAL TYPE AND QUANTITY | THREADED STUD 4 |
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| AJEC | BOSS HEIGHT | INCHES NOMINAL 0.140 |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | ALL LOCATIONS AC 240.0 |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | ALL LOCATIONS AC 1000.0 |
Supersedes
This item replaces cancelled NIINs 004585100 · 009657250 · 010499180 · 011574606. An older drawing citing one of those numbers resolves here.