Home / MS parts / NSN 5925-01-177-3177
NSN 5925-01-177-3177  ·  NIIN 011773177  ·  FSC 5925
NO DASHES 5925011773177
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

29 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
AAQLBODY STYLE
ABHPOVERALL LENGTHINCHES NOMINAL 2.000
ABKWOVERALL HEIGHTINCHES NOMINAL 1.320
ABMKOVERALL WIDTHINCHES NOMINAL 1.777
AFJNFRAGILITY FACTORMODERATELY RUGGED
AKPXPOLE QUANTITY2
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
AXHRMOUNTING FACILITY TYPE AND QUANTITYCLAMP 2
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
BBRJSPECIAL HANDLING FEATUREMAGNETIC
CBBLFEATURES PROVIDEDCURRENT LIMITER
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES DC 5.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS DC 50.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS DC 1000.0
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
CPRJTRIP RELEASE METHODALL LOCATIONS MAGNETIC-HYDRAULIC
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS INSTANTANEOUS AND TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONBETWEEN POLE ONE AND TWO
CPSMINTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 0.050 AND MAXIMUM AT 200 PCT 0.900
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDGENERAL PURPOSE
CTJSUNPACKAGED UNIT WEIGHTOUNCES NOMINAL 0.180
MATTMATERIALCASE PLASTIC
TTQYTERMINAL TYPE AND QUANTITYTAB, SOLDER LUG 2