Home / MS parts / NSN 5925-01-299-3672
NSN 5925-01-299-3672  ·  NIIN 012993672  ·  FSC 5925
NO DASHES 5925012993672
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

36 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
AAQLBODY STYLE
ADAQBODY LENGTHINCHES MINIMUM 5.785 AND INCHES MAXIMUM 5.815
ADATBODY WIDTHINCHES MAXIMUM 2.072
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES MINIMUM 3.535 AND INCHES MAXIMUM 3.565
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES MINIMUM 1.011 AND INCHES MAXIMUM 1.041
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES MINIMUM 2.735 AND INCHES MAXIMUM 2.765
AEHADISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES MINIMUM 1.011 AND INCHES MAXIMUM 1.041
AFJNFRAGILITY FACTORMODERATELY RUGGED
AJECBOSS HEIGHTINCHES MINIMUM 0.205 AND INCHES MAXIMUM 0.235
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES MINIMUM 3.535 AND INCHES MAXIMUM 3.565
AKPXPOLE QUANTITY2
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 4
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
CMLPTHREAD QUANTITY PER INCH32
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 20.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 480.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 1000.0
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
CPRJTRIP RELEASE METHODALL LOCATIONS MAGNETIC
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 2
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONAT EACH POLE
CPRYEXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE AND TWO LINKED
CPSMINTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
CQJXNOMINAL THREAD SIZEINCHES 0.138
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 2.000 AND MAXIMUM AT 200 PCT 18.000
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDDUSTPROOF
FREQFREQUENCY IN HERTZ50.0 OR 60.0
MATTMATERIALCASE PLASTIC
THSDTHREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
TTQYTERMINAL TYPE AND QUANTITYTHREADED STUD 4