NSN 5925-00-080-2163 · NIIN 000802163 · FSC 5925
NO DASHES 5925000802163
In Stock
CIRCUIT BREAKER
Circuit Breakers
Technical characteristics
31 rows
Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.
| MRC | Requirement | Value |
|---|---|---|
| CPRH | CIRCUIT PROTECTION TYPE | ALL LOCATIONS OVERCURRENT |
| CRCF | TRIP RELEASE AMBIENT TEMP RATING | ALL LOCATIONS CELSIUS NOMINAL 40.0 |
| TEST | TEST DATA DOCUMENT | SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.). 81348-W-C-375 |
| TTQY | TERMINAL TYPE AND QUANTITY | CLIP 3 AND COMPRESSION 3 |
| ZZZK | SPECIFICATION/STANDARD DATA | GOVERNMENT SPECIFICATION 81348-W-C-375 TO 3 |
| AKPX | POLE QUANTITY | 3 |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | TERMINAL 6 |
| CPRJ | TRIP RELEASE METHOD | ALL LOCATIONS THERMAL-MAGNETIC |
| CPRL | TRIP RELEASE CHARACTERISTIC | ALL LOCATIONS TIME DELAY |
| AAQL | BODY STYLE | |
| ADAQ | BODY LENGTH | INCHES NOMINAL 3.000 |
| ADAT | BODY WIDTH | INCHES NOMINAL 2.230 |
| ADAU | BODY HEIGHT | INCHES NOMINAL 2.580 |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | TOGGLE 1 |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | ALL LOCATIONS MAXIMUM AT 200 PCT 4.000 |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | CORROSION RESISTANT |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | ALL LOCATIONS AMPERES AC 40.0 |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | ALL LOCATIONS AC 240.0 |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | ALL LOCATIONS AC 10000.0 |
| CPRQ | RESET METHOD | MANUAL |
| FREQ | FREQUENCY IN HERTZ | 60.0 |
| MATT | MATERIAL | CASE PLASTIC |
| AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | INCHES NOMINAL 0.740 |
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 135.0 |
| AJEC | BOSS HEIGHT | INCHES NOMINAL 0.250 |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
Supersedes
This item replaces cancelled NIIN 009897297. An older drawing citing one of those numbers resolves here.