Home / MS parts / NSN 5925-01-156-4426
NSN 5925-01-156-4426  ·  NIIN 011564426  ·  FSC 5925
NO DASHES 5925011564426
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

40 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
AAQLBODY STYLE
ADAQBODY LENGTHINCHES NOMINAL 5.125
ADATBODY WIDTHINCHES MAXIMUM 3.108
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 3.550
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 1.026
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES NOMINAL 2.750
AEGJSWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
AEHADISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES NOMINAL 1.026
AJECBOSS HEIGHTINCHES NOMINAL 0.220
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES NOMINAL 3.550
AKPXPOLE QUANTITY3
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 6
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 20.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 277.0 AND AC 480.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 5000.0
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
CPRJTRIP RELEASE METHODALL LOCATIONS MAGNETIC-HYDRAULIC
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
CPRPULTIMATE TRIP TIME PER POLE IN SECONDSALL LOCATIONS MAXIMUM 800.000
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 3
CPRWACTUATOR FUNCTIONRESET
CPRXACTUATOR POSITION DESIGNATIONAT EACH POLE
CPRYEXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED
CPRZAUXILIARY SWITCH FUNCTION AND QUANTITYCONTROL 1
CPSMINTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
CQJXNOMINAL THREAD SIZEINCHES 0.138
CQSMSWITCH LOCATION AND POSITION DESIGNATIONEXTERNAL AT POLE ONE
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 125 PCT 70.000 AND MAXIMUM AT 125 PCT 800.000 AND MINIMUM AT 200 PCT 20.000 AND MAXIMUM AT 200 PCT 130.000 AND MINIMUM AT 400 PCT 4.000 AND MAXIMUM AT 400 PCT 18.000 AND MINIMUM AT 1000 PCT 0.012 AND MAXIMUM AT 1000 PCT 0.080
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND MOISTURE RESISTANT
CRTKSWITCH TERMINAL TYPETAB, SOLDER LUG
CSSXSWITCH CURRENT RATING AND TYPE IN AMPSAC 10.0
CSWPSWITCH VOLTAGE RATING AND TYPE IN VOLTSAC 250.0
FEATSPECIAL FEATURESANTI-FLASHOVER BARRIER BETWEEN POLES
FREQFREQUENCY IN HERTZ50.0 OR 60.0
MATTMATERIALCASE PLASTIC
THSDTHREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
TTQYTERMINAL TYPE AND QUANTITYTHREADED STUD 6