Home / MS parts / NSN 5925-01-161-9560
NSN 5925-01-161-9560  ·  NIIN 011619560  ·  FSC 5925
NO DASHES 5925011619560
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

57 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
AAQLBODY STYLE
ABTDMOUNTING SLOT WIDTHINCHES NOMINAL 0.164
ADAQBODY LENGTHINCHES NOMINAL 5.844
ADATBODY WIDTHINCHES NOMINAL 4.128
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 3.546
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 1.032
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES NOMINAL 2.750
AEHADISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES NOMINAL 1.032
AFJNFRAGILITY FACTORMODERATELY RUGGED
AJECBOSS HEIGHTINCHES NOMINAL 0.218
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES NOMINAL 2.609
AKPXPOLE QUANTITY4
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 8 AND SLOT 8
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
BBRJSPECIAL HANDLING FEATUREMAGNETIC
CMLPTHREAD QUANTITY PER INCH32
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLESECOND LOCATION AMPERES AC 100.0
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEFIRST LOCATION AMPERES AC 100.0
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLETHIRD LOCATION AMPERES AC 100.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSSECOND LOCATION AC 240.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSFOURTH LOCATION DC 115.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSTHIRD LOCATION AC 240.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSFIRST LOCATION AC 240.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSSECOND LOCATION AC 5000.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSFIRST LOCATION AC 5000.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSTHIRD LOCATION AC 5000.0
CPRHCIRCUIT PROTECTION TYPESECOND LOCATION OVERCURRENT
CPRHCIRCUIT PROTECTION TYPEFOURTH LOCATION UNDERVOLTAGE
CPRHCIRCUIT PROTECTION TYPETHIRD LOCATION OVERCURRENT
CPRHCIRCUIT PROTECTION TYPEFIRST LOCATION OVERCURRENT
CPRJTRIP RELEASE METHODALL LOCATIONS MAGNETIC-HYDRAULIC
CPRLTRIP RELEASE CHARACTERISTICSECOND LOCATION TIME DELAY
CPRLTRIP RELEASE CHARACTERISTICFIRST LOCATION TIME DELAY
CPRLTRIP RELEASE CHARACTERISTICFOURTH LOCATION INSTANTANEOUS
CPRLTRIP RELEASE CHARACTERISTICTHIRD LOCATION TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT150.0
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 4
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONAT EACH POLE
CPRYEXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, THREE, AND FOUR LINKED
CPSMINTERNAL TRIP RELEASE CONFIGURATIONSECOND LOCATION SERIES TRIP
CPSMINTERNAL TRIP RELEASE CONFIGURATIONFOURTH LOCATION SHUNT TRIP
CPSMINTERNAL TRIP RELEASE CONFIGURATIONTHIRD LOCATION SERIES TRIP
CPSMINTERNAL TRIP RELEASE CONFIGURATIONFIRST LOCATION SERIES TRIP
CQJXNOMINAL THREAD SIZEINCHES 0.138
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTSECOND LOCATION MINIMUM AT 200 PCT 20.000 AND MAXIMUM AT 200 PCT 100.000
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTFIRST LOCATION MINIMUM AT 200 PCT 20.000 AND MAXIMUM AT 200 PCT 100.000
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTTHIRD LOCATION MINIMUM AT 200 PCT 20.000 AND MAXIMUM AT 200 PCT 100.000
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND MOISTURE RESISTANT
CTJSUNPACKAGED UNIT WEIGHTPOUNDS NOMINAL 2.700
FREQFREQUENCY IN HERTZ400.0
MATTMATERIALCASE PLASTIC
THSDTHREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
TTQYTERMINAL TYPE AND QUANTITYTHREADED STUD 8