NSN 5925-00-841-0679 · NIIN 008410679 · FSC 5925
NO DASHES 5925008410679
In Stock
CIRCUIT BREAKER
Circuit Breakers
Technical characteristics
34 rows
Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.
| MRC | Requirement | Value |
|---|---|---|
| AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | INCHES NOMINAL 1.810 |
| AKPX | POLE QUANTITY | 3 |
| CPRJ | TRIP RELEASE METHOD | ALL LOCATIONS THERMAL |
| CPRL | TRIP RELEASE CHARACTERISTIC | ALL LOCATIONS TIME DELAY |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 145.0 |
| ABXD | BUSHING LENGTH | INCHES NOMINAL 0.281 |
| TTQY | TERMINAL TYPE AND QUANTITY | TAB W/SCREW 6 |
| ADAU | BODY HEIGHT | INCHES MAXIMUM 2.765 |
| ADAQ | BODY LENGTH | INCHES MAXIMUM 0.850 |
| ADAT | BODY WIDTH | INCHES MAXIMUM 2.000 |
| AAQL | BODY STYLE | |
| AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | INCHES NOMINAL 1.625 |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | INCHES NOMINAL 0.750 |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | ALL LOCATIONS AC 800.0 |
| THSD | THREAD SERIES DESIGNATOR | UNEF AND UNIFIED NATIONAL COARSE (UNC) |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | THREADED BUSHING 1 AND THREADED HOLE(S) 4 |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| CMLP | THREAD QUANTITY PER INCH | 32 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | ALL LOCATIONS AMPERES AC 5.0 |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | ALL LOCATIONS AC 120.0 |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | ALL LOCATIONS SERIES TRIP |
| FREQ | FREQUENCY IN HERTZ | 60.0 |
| CPRH | CIRCUIT PROTECTION TYPE | ALL LOCATIONS OVERCURRENT |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | PUSH-PULL 1 |
| CRCF | TRIP RELEASE AMBIENT TEMP RATING | ALL LOCATIONS CELSIUS NOMINAL 25.0 |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | INCHES NOMINAL 0.750 |
| MATT | MATERIAL | CASE PLASTIC |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | ALL LOCATIONS MINIMUM AT 200 PCT 4.000 AND MAXIMUM AT 200 PCT 35.000 |
| CQJX | NOMINAL THREAD SIZE | INCHES 0.375 AND INCHES 0.138 |