CIRCUIT BREAKER
Circuit Breakers
Technical characteristics
37 rows
Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.
| MRC | Requirement | Value |
|---|---|---|
| CMLP | THREAD QUANTITY PER INCH | 32 |
| CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | THREADED HOLE(S) 6 |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | ALL LOCATIONS SERIES TRIP |
| CQJX | NOMINAL THREAD SIZE | INCHES 0.138 |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | ALL LOCATIONS MINIMUM AT 200 PCT 3.000 AND MAXIMUM AT 200 PCT 9.000 AND MINIMUM AT 300 PCT 0.800 AND MAXIMUM AT 300 PCT 2.500 AND MINIMUM AT 400 PCT 0.400 AND MAXIMUM AT 400 PCT 1.000 |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | INCHES NOMINAL 2.611 |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| AJEC | BOSS HEIGHT | INCHES NOMINAL 0.140 |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 115.0 |
| AKPX | POLE QUANTITY | 3 |
| AAJE | THREAD PITCH DIAMETERS | INCHES 0.1177 TO 0.1214 |
| AAQL | BODY STYLE | |
| ADAQ | BODY LENGTH | INCHES NOMINAL 2.500 |
| ADAT | BODY WIDTH | INCHES NOMINAL 2.250 |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | INCHES NOMINAL 1.938 |
| AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | INCHES NOMINAL 0.750 |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | INCHES NOMINAL 2.062 |
| AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | INCHES NOMINAL 0.750 |
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND MOISTURE RESISTANT |
| CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
| APNQ | ARC QUENCHING METHOD | AIR |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | ALL LOCATIONS AC 1000.0 |
| CPRH | CIRCUIT PROTECTION TYPE | ALL LOCATIONS OVERCURRENT |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| THSD | THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | ALL LOCATIONS AMPERES AC 10.0 |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | ALL LOCATIONS AC 250.0 |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | TOGGLE 3 |
| FREQ | FREQUENCY IN HERTZ | 400.0 |
| MATT | MATERIAL | CASE PLASTIC |
| CPRJ | TRIP RELEASE METHOD | ALL LOCATIONS MAGNETIC-HYDRAULIC |
| CPRL | TRIP RELEASE CHARACTERISTIC | ALL LOCATIONS TIME DELAY |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRQ | RESET METHOD | MANUAL |
| TTQY | TERMINAL TYPE AND QUANTITY | THREADED STUD 6 |