Home / MS parts / NSN 5925-01-161-2945
NSN 5925-01-161-2945  ·  NIIN 011612945  ·  FSC 5925
NO DASHES 5925011612945
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

50 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
AAQLBODY STYLE
ADAQBODY LENGTHINCHES MINIMUM 5.769 AND INCHES MAXIMUM 5.831
ADATBODY WIDTHINCHES MINIMUM 2.041 AND INCHES MAXIMUM 2.103
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES MINIMUM 3.516 AND INCHES MAXIMUM 3.578
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES MINIMUM 0.995 AND INCHES MAXIMUM 1.057
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES MINIMUM 2.719 AND INCHES MAXIMUM 2.781
AEGJSWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
AEHADISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES MINIMUM 0.995 AND INCHES MAXIMUM 1.057
AFJNFRAGILITY FACTORMODERATELY RUGGED
AJECBOSS HEIGHTINCHES MINIMUM 0.209 AND INCHES MAXIMUM 0.229
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES MINIMUM 3.172 AND INCHES MAXIMUM 3.265
AKPXPOLE QUANTITY2
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 4
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
BBRJSPECIAL HANDLING FEATUREMAGNETIC
CBBLFEATURES PROVIDEDHIGH INRUSH PROTECTION
CMLPTHREAD QUANTITY PER INCH32
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEFIRST LOCATION AMPERES AC 15.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSSECOND LOCATION DC 24.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSFIRST LOCATION AC 240.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSFIRST LOCATION AC 5000.0
CPRHCIRCUIT PROTECTION TYPESECOND LOCATION OVERVOLTAGE
CPRHCIRCUIT PROTECTION TYPEFIRST LOCATION OVERCURRENT
CPRJTRIP RELEASE METHODFIRST LOCATION MAGNETIC-HYDRAULIC
CPRLTRIP RELEASE CHARACTERISTICSECOND LOCATION INSTANTANEOUS
CPRLTRIP RELEASE CHARACTERISTICFIRST LOCATION TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT120.0
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 2
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONAT EACH POLE
CPRYEXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE AND TWO LINKED
CPRZAUXILIARY SWITCH FUNCTION AND QUANTITYALARM 1
CPSMINTERNAL TRIP RELEASE CONFIGURATIONFIRST LOCATION SERIES TRIP
CPSMINTERNAL TRIP RELEASE CONFIGURATIONSECOND LOCATION RELAY TRIP
CQJXNOMINAL THREAD SIZEINCHES 0.138
CQSMSWITCH LOCATION AND POSITION DESIGNATIONEXTERNAL AT POLE ONE
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTFIRST LOCATION MINIMUM AT 200 PCT 15.000 AND MAXIMUM AT 200 PCT 70.000
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDDUSTPROOF
CRTKSWITCH TERMINAL TYPETURRET
CSSXSWITCH CURRENT RATING AND TYPE IN AMPSAC 2.5 AND DC 1.0
CSWPSWITCH VOLTAGE RATING AND TYPE IN VOLTSAC 250.0 AND DC 50.0
CTJSUNPACKAGED UNIT WEIGHTOUNCES NOMINAL 11.000
FREQFREQUENCY IN HERTZ50.0 OR 60.0
MATTMATERIALCASE PLASTIC
THSDTHREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
TTQYTERMINAL TYPE AND QUANTITYTHREADED STUD 6