Home / MS parts / NSN 5925-00-665-7946
NSN 5925-00-665-7946  ·  NIIN 006657946  ·  FSC 5925
NO DASHES 5925006657946
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

34 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 5.062
CPRWACTUATOR FUNCTIONTRIP-RESET
TTQYTERMINAL TYPE AND QUANTITYCOMPRESSION 4
FREQFREQUENCY IN HERTZ60.0
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
AEBVUNTHREADED MOUNTING HOLE DIAMETERINCHES NOMINAL 0.188
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES NOMINAL 4.500
AFJNFRAGILITY FACTORMODERATELY RUGGED
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES NOMINAL 3.375
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
CPRQRESET METHODMANUAL
AAQLBODY STYLE
ABXDBUSHING LENGTHINCHES NOMINAL 0.125
ADAQBODY LENGTHINCHES NOMINAL 6.000
CPRXACTUATOR POSITION DESIGNATIONAT POLE TWO
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 1.375
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
AXHRMOUNTING FACILITY TYPE AND QUANTITYUNTHREADED HOLE(S) 2
MATTMATERIALCASE PLASTIC
ADATBODY WIDTHINCHES NOMINAL 2.750
CRCFTRIP RELEASE AMBIENT TEMP RATINGALL LOCATIONS CELSIUS NOMINAL 40.0
AKPXPOLE QUANTITY2
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
CPRJTRIP RELEASE METHODALL LOCATIONS THERMAL-MAGNETIC
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 30.000 AND MAXIMUM AT 200 PCT 60.000
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDDUSTPROOF AND GENERAL PURPOSE AND FUNGUS RESISTANT
BBRJSPECIAL HANDLING FEATUREMAGNETIC
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 35.0 AND AMPERES DC 35.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 240.0 AND DC 250.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 10000.0 AND DC 5000.0
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
CTJSUNPACKAGED UNIT WEIGHTPOUNDS NOMINAL 3.000
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE

Supersedes

This item replaces cancelled NIIN 001740370. An older drawing citing one of those numbers resolves here.