NSN 5925-00-963-4042 · NIIN 009634042 · FSC 5925
NO DASHES 5925009634042
In Stock
CIRCUIT BREAKER
Circuit Breakers
Technical characteristics
25 rows
Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.
| MRC | Requirement | Value |
|---|---|---|
| TTQY | TERMINAL TYPE AND QUANTITY | SCREW 2 |
| CQJX | NOMINAL THREAD SIZE | INCHES 0.469 |
| CRCF | TRIP RELEASE AMBIENT TEMP RATING | SINGLE LOCATION CELSIUS NOMINAL 25.0 |
| MATT | MATERIAL | CASE PLASTIC |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | TOGGLE 1 |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | THREADED BUSHING 1 |
| THSD | THREAD SERIES DESIGNATOR | UNS |
| CPRL | TRIP RELEASE CHARACTERISTIC | SINGLE LOCATION INSTANTANEOUS AND TIME DELAY |
| ABHP | OVERALL LENGTH | INCHES NOMINAL 2.337 |
| ABKW | OVERALL HEIGHT | INCHES NOMINAL 0.750 |
| ABMK | OVERALL WIDTH | INCHES NOMINAL 1.094 |
| AKPX | POLE QUANTITY | 1 |
| APNQ | ARC QUENCHING METHOD | AIR |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | SINGLE LOCATION AMPERES AC 15.0 AND AMPERES DC 15.0 |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | SINGLE LOCATION AC 200.0 AND DC 28.0 |
| ZZZK | SPECIFICATION/STANDARD DATA | MANUFACTURERS SPECIFICATION 36659-613540-1 |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | SINGLE LOCATION MINIMUM AT 150 PCT 60.000 AND MAXIMUM AT 150 PCT 900.000 AND MINIMUM AT 200 PCT 18.000 AND MAXIMUM AT 200 PCT 50.000 AND MINIMUM AT 300 PCT 6.000 AND MAXIMUM AT 300 PCT 20.000 |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | EXPLOSION PROOF |
| CPRH | CIRCUIT PROTECTION TYPE | SINGLE LOCATION OVERCURRENT |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 116.0 |
| CMLP | THREAD QUANTITY PER INCH | 32 |
| CPRJ | TRIP RELEASE METHOD | SINGLE LOCATION THERMAL |