NSN 5925-00-080-9284 · NIIN 000809284 · FSC 5925
NO DASHES 5925000809284
In Stock
CIRCUIT BREAKER
Circuit Breakers
Technical characteristics
37 rows
Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.
| MRC | Requirement | Value |
|---|---|---|
| CRCF | TRIP RELEASE AMBIENT TEMP RATING | SINGLE LOCATION CELSIUS NOMINAL 24.0 |
| CQSM | SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE ONE |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | SINGLE LOCATION MINIMUM AT 200 PCT 23.000 AND MAXIMUM AT 300 PCT 4.400 |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SINGLE LOCATION SERIES TRIP W/DUAL RATING |
| CQJX | NOMINAL THREAD SIZE | INCHES 0.138 |
| CPRZ | AUXILIARY SWITCH FUNCTION AND QUANTITY | ALARM 1 |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | PUSH BUTTON 1 |
| CPRW | ACTUATOR FUNCTION | TRIP W/SEPARATE RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
| AAQL | BODY STYLE | |
| ABHP | OVERALL LENGTH | INCHES NOMINAL 1.969 |
| ABMK | OVERALL WIDTH | INCHES NOMINAL 0.993 |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | INCHES NOMINAL 1.340 |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | INCHES NOMINAL 1.000 |
| AEGJ | SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
| AJEC | BOSS HEIGHT | INCHES NOMINAL 0.120 |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | INCHES NOMINAL 1.910 |
| CRTK | SWITCH TERMINAL TYPE | SCREW |
| CSSX | SWITCH CURRENT RATING AND TYPE IN AMPS | AC 3.0 AND DC 3.0 |
| CSWP | SWITCH VOLTAGE RATING AND TYPE IN VOLTS | AC 115.0 AND DC 50.0 |
| FREQ | FREQUENCY IN HERTZ | 400.0 |
| MATT | MATERIAL | CASE PLASTIC |
| THSD | THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| TTQY | TERMINAL TYPE AND QUANTITY | EYELET 3 |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | SINGLE LOCATION AC 230.0 AND DC 120.0 |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | SINGLE LOCATION AC 200.0 AND DC 200.0 |
| CPRH | CIRCUIT PROTECTION TYPE | SINGLE LOCATION OVERCURRENT |
| CPRJ | TRIP RELEASE METHOD | SINGLE LOCATION THERMAL |
| CPRL | TRIP RELEASE CHARACTERISTIC | SINGLE LOCATION TIME DELAY |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 135.0 |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| CMLP | THREAD QUANTITY PER INCH | 32 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | SINGLE LOCATION AMPERES AC 4.0 AND AMPERES DC 4.0 |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | THREADED HOLE(S) 2 |
| AKPX | POLE QUANTITY | 1 |