CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

36 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
CPRXACTUATOR POSITION DESIGNATIONAT EACH POLE
CPRWACTUATOR FUNCTIONTRIP-RESET
AAQLBODY STYLE
ABXDBUSHING LENGTHINCHES MINIMUM 0.146 AND INCHES MAXIMUM 0.166
ADAQBODY LENGTHINCHES MINIMUM 2.490 AND INCHES MAXIMUM 2.510
ADATBODY WIDTHINCHES MINIMUM 2.263 AND INCHES MAXIMUM 2.283
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES MINIMUM 1.180 AND INCHES MAXIMUM 1.200
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES MINIMUM 0.740 AND INCHES MAXIMUM 0.760
TTQYTERMINAL TYPE AND QUANTITYTAB W/SCREW 6
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES MINIMUM 1.802 AND INCHES MAXIMUM 1.822
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT400.0
CPRYEXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED
CPSMINTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
CQJXNOMINAL THREAD SIZEINCHES 0.138
AEHADISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES MINIMUM 0.740 AND INCHES MAXIMUM 0.760
AFJNFRAGILITY FACTORMODERATELY RUGGED
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES MINIMUM 1.990 AND INCHES MAXIMUM 2.010
AKPXPOLE QUANTITY3
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 6
CMLPTHREAD QUANTITY PER INCH32
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 3.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 208.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 3500.0
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
CPRJTRIP RELEASE METHODALL LOCATIONS MAGNETIC-HYDRAULIC
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 2.500 AND MAXIMUM AT 200 PCT 9.500
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDDUSTPROOF AND FUNGUS PROOF
FREQFREQUENCY IN HERTZ60.0
MATTMATERIALCASE PLASTIC
THSDTHREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 3
CPRQRESET METHODMANUAL

Cross-references

3 manufacturer part numbers on file for this NSN — each shown against the CAGE code it belongs to.

Manufacturer cross-reference part numbers and CAGE codes
Manufacturer part numberCAGE
3XAM17-3-208VAC400C5574193
138C206H0197942
DMS 83059B16236