NSN 5925-00-106-5210 · NIIN 001065210 · FSC 5925
NO DASHES 5925001065210
In Stock
CIRCUIT BREAKER
Circuit Breakers
Technical characteristics
30 rows
Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.
| MRC | Requirement | Value |
|---|---|---|
| TEST | TEST DATA DOCUMENT | SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.). 81349--IL-C-39019 |
| THSD | THREAD SERIES DESIGNATOR | UNEF |
| TTQY | TERMINAL TYPE AND QUANTITY | WIRE HOOK 2 |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | INCHES MAXIMUM 1.700 |
| AKPX | POLE QUANTITY | 1 |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | TOGGLE 1 |
| FREQ | FREQUENCY IN HERTZ | 60.0 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | SINGLE LOCATION AMPERES AC 2.0 |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | SINGLE LOCATION AC 240.0 |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | SINGLE LOCATION AC 300.0 |
| CPRH | CIRCUIT PROTECTION TYPE | SINGLE LOCATION OVERCURRENT |
| CPRJ | TRIP RELEASE METHOD | SINGLE LOCATION MAGNETIC |
| CPRL | TRIP RELEASE CHARACTERISTIC | SINGLE LOCATION TIME DELAY |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 115.0 |
| CPRQ | RESET METHOD | MANUAL |
| AAJE | THREAD PITCH DIAMETERS | INCHES 0.3503 TO 0.3537 |
| AAQL | BODY STYLE | |
| ABXD | BUSHING LENGTH | INCHES MAXIMUM 0.380 |
| ADAQ | BODY LENGTH | INCHES MAXIMUM 1.562 |
| ADAT | BODY WIDTH | INCHES MAXIMUM 0.625 |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | INCHES MAXIMUM 0.906 |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | SINGLE LOCATION MINIMUM AT 200 PCT 0.500 AND MAXIMUM AT 200 PCT 9.000 AND MAXIMUM AT 400 PCT 1.750 |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND HERMETICALLY SEALED |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | THREADED BUSHING 1 |
| CMLP | THREAD QUANTITY PER INCH | 32 |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SINGLE LOCATION SERIES TRIP |
| CQJX | NOMINAL THREAD SIZE | INCHES 0.375 |
Cross-references
6 manufacturer part numbers on file for this NSN — each shown against the CAGE code it belongs to.
| Manufacturer part number | CAGE |
|---|---|
| G330014S17 | 24930 |
| HB1Z1-84 | 74193 |
| MIL-C-39019/1 | 81349 |
| M39019/01-84 | 81349 |
| AP1-163-17 | 81541 |
| AP1-1-6-2-202 | 81541 |