NSN 5925-00-109-9161 · NIIN 001099161 · FSC 5925
NO DASHES 5925001099161
In Stock
CIRCUIT BREAKER
Circuit Breakers
Technical characteristics
19 rows
Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.
| MRC | Requirement | Value |
|---|---|---|
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | ALL LOCATIONS AMPERES AC 800.0 |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | UNTHREADED HOLE(S) 4 |
| AKPX | POLE QUANTITY | 3 |
| CPRL | TRIP RELEASE CHARACTERISTIC | ALL LOCATIONS TIME DELAY |
| CRCF | TRIP RELEASE AMBIENT TEMP RATING | ALL LOCATIONS CELSIUS NOMINAL 40.0 |
| FEAT | SPECIAL FEATURES | MAIN CONTACTS PROTECTED BY ARCING CONTACTS,ARC BARRIERS AND MAGNETIC BLOWOUTS; MAIN CONTACTS SELF-ALIGNING,SELF-CLEANING AND REMOVABLE |
| FREQ | FREQUENCY IN HERTZ | 60.0 |
| SPCL | SPECIAL TEST FEATURES | DIELECTRIC STRENGTH MUST PASS EQUIVALENT OF 1960V BETWEEN LIVE PARTS AND GROUND AND BETWEEN POLES FOR 1 SECOND IN BOTH OPEN AND CLOSED POSITIONS; MUST INTERRUPT 350 PERCENT AT 60 HZ OF ITS RATED CURRENT AT 208V FOR 30 OPERATIONS AT 10 SECOND INTERVALS WITHOUT UNDUE BURNING OF CONTACTS |
| AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | INCHES NOMINAL 2.750 |
| CPRQ | RESET METHOD | MANUAL |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | TOGGLE 1 |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | ALL LOCATIONS MINIMUM AT 200 PCT 280.000 AND MAXIMUM AT 200 PCT 950.000 |
| AEBV | UNTHREADED MOUNTING HOLE DIAMETER | INCHES NOMINAL 1.031 |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | INCHES NOMINAL 14.750 |
| AAQL | BODY STYLE | |
| ADAQ | BODY LENGTH | INCHES NOMINAL 17.000 |
| ADAT | BODY WIDTH | INCHES MINIMUM 8.000 AND INCHES MAXIMUM 8.500 |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | ALL LOCATIONS AC 10000.0 |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | ALL LOCATIONS AC 600.0 |