NSN 5925-00-407-2184 · NIIN 004072184 · FSC 5925
NO DASHES 5925004072184
In Stock
CIRCUIT BREAKER
Circuit Breakers
Technical characteristics
38 rows
Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.
| MRC | Requirement | Value |
|---|---|---|
| AAJE | THREAD PITCH DIAMETERS | INCHES 0.1177 TO 0.1214 |
| FREQ | FREQUENCY IN HERTZ | 60.0 |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| CMLP | THREAD QUANTITY PER INCH | 32 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | SINGLE LOCATION AMPERES AC 15.0 |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | SINGLE LOCATION AC 115.0 |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | SINGLE LOCATION AC 1000.0 |
| MATT | MATERIAL | CASE PLASTIC |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | TOGGLE 1 |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
| CPRH | CIRCUIT PROTECTION TYPE | SINGLE LOCATION OVERCURRENT |
| CPRJ | TRIP RELEASE METHOD | SINGLE LOCATION MAGNETIC-HYDRAULIC |
| CPRL | TRIP RELEASE CHARACTERISTIC | SINGLE LOCATION TIME DELAY |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 115.0 |
| CPRP | ULTIMATE TRIP TIME PER POLE IN SECONDS | SINGLE LOCATION MAXIMUM 80.000 |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| ADAT | BODY WIDTH | INCHES MINIMUM 0.740 AND INCHES MAXIMUM 0.760 |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | INCHES MINIMUM 1.928 AND INCHES MAXIMUM 1.948 |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | INCHES MINIMUM 2.052 AND INCHES MAXIMUM 2.072 |
| AEGJ | SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| CQSM | SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE ONE |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | SINGLE LOCATION MINIMUM AT 200 PCT 4.000 AND MAXIMUM AT 200 PCT 10.000 |
| CRTK | SWITCH TERMINAL TYPE | TAB, SOLDER LUG |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | THREADED HOLE(S) 2 |
| AAQL | BODY STYLE | |
| ADAQ | BODY LENGTH | INCHES MINIMUM 2.490 AND INCHES MAXIMUM 2.510 |
| TTQY | TERMINAL TYPE AND QUANTITY | THREADED STUD 2 |
| AJEC | BOSS HEIGHT | INCHES MINIMUM 0.130 AND INCHES MAXIMUM 0.150 |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | INCHES MINIMUM 2.461 AND INCHES MAXIMUM 2.481 |
| AKPX | POLE QUANTITY | 1 |
| APNQ | ARC QUENCHING METHOD | AIR |
| THSD | THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| CPRZ | AUXILIARY SWITCH FUNCTION AND QUANTITY | ALARM 1 |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SINGLE LOCATION SERIES TRIP |
| CQJX | NOMINAL THREAD SIZE | INCHES 0.138 |
Cross-references
4 manufacturer part numbers on file for this NSN — each shown against the CAGE code it belongs to.
| Manufacturer part number | CAGE |
|---|---|
| 70-342-10-15-250AC-60-4 | 74193 |
| 70-342-10-15-250VAC-60-4 | 74193 |
| APL1R1195-18 | 81541 |
| 990C780H18 | 18323 |