Home / MS parts / NSN 5925-00-491-6536
NSN 5925-00-491-6536  ·  NIIN 004916536  ·  FSC 5925
NO DASHES 5925004916536
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

34 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
CPRXACTUATOR POSITION DESIGNATIONAT POLE TWO
FREQFREQUENCY IN HERTZ60.0
MATTMATERIALCASE PLASTIC
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
ADAUBODY HEIGHTINCHES NOMINAL 3.375
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDDUSTPROOF AND GENERAL PURPOSE
CRCFTRIP RELEASE AMBIENT TEMP RATINGALL LOCATIONS CELSIUS NOMINAL 40.0
CPRWACTUATOR FUNCTIONTRIP-RESET
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 1.375
AEBVUNTHREADED MOUNTING HOLE DIAMETERINCHES NOMINAL 0.188
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES NOMINAL 4.500
AEHADISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES NOMINAL 1.375
AFJNFRAGILITY FACTORMODERATELY RUGGED
AJECBOSS HEIGHTINCHES NOMINAL 0.125
AKPXPOLE QUANTITY3
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
AXHRMOUNTING FACILITY TYPE AND QUANTITYUNTHREADED HOLE(S) 4
TTQYTERMINAL TYPE AND QUANTITYCOMPRESSION 6
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 5.062
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
CPRJTRIP RELEASE METHODALL LOCATIONS THERMAL-MAGNETIC
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 28.000 AND MAXIMUM AT 200 PCT 75.000
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 10000.0 AND DC 5000.0
AAQLBODY STYLE
ADAQBODY LENGTHINCHES NOMINAL 6.000
ADATBODY WIDTHINCHES NOMINAL 4.125
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 240.0 AND DC 250.0
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 25.0 AND AMPERES DC 25.0
CPRQRESET METHODMANUAL
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
BBRJSPECIAL HANDLING FEATUREMAGNETIC

Cross-references

3 manufacturer part numbers on file for this NSN — each shown against the CAGE code it belongs to.

Manufacturer cross-reference part numbers and CAGE codes
Manufacturer part numberCAGE
99902479500
4990D03G3689946
EB302589946

Supersedes

This item replaces cancelled NIINs 001755247 · 006814699. An older drawing citing one of those numbers resolves here.