32 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 240.0
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 20.0
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
AJECBOSS HEIGHTINCHES NOMINAL 0.250
AKPXPOLE QUANTITY2
AXHRMOUNTING FACILITY TYPE AND QUANTITYTERMINAL 4
AAQLBODY STYLE
ADAQBODY LENGTHINCHES NOMINAL 3.094
ADATBODY WIDTHINCHES NOMINAL 2.000
ADAUBODY HEIGHTINCHES NOMINAL 2.812
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 1.000
AFJNFRAGILITY FACTORMODERATELY RUGGED
TESTTEST DATA DOCUMENTSPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.). 81348-W-C-375
TTQYTERMINAL TYPE AND QUANTITYCOMPRESSION 2 AND QUICK DISCONNECT, MALE 2
ZZZKSPECIFICATION/STANDARD DATAGOVERNMENT SPECIFICATION 81348-W-C-375 TO 14
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT
CRCFTRIP RELEASE AMBIENT TEMP RATINGALL LOCATIONS CELSIUS NOMINAL 40.0
FREQFREQUENCY IN HERTZ60.0
MATTMATERIALCASE PLASTIC
CPRWACTUATOR FUNCTIONTRIP-RESET
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MAXIMUM AT 200 PCT 120.000
CPRYEXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE AND TWO LINKED
CPRQRESET METHODMANUAL
CPRXACTUATOR POSITION DESIGNATIONAT EACH POLE
CPSMINTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 10000.0
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
CPRJTRIP RELEASE METHODALL LOCATIONS THERMAL
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS INSTANTANEOUS AND TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 2
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE

Cross-references

3 manufacturer part numbers on file for this NSN — each shown against the CAGE code it belongs to.

Manufacturer cross-reference part numbers and CAGE codes
Manufacturer part numberCAGE
W-C-375/1481348
WC375/14-00281348
22095201