Home / MS parts / NSN 5925-00-816-5263
NSN 5925-00-816-5263  ·  NIIN 008165263  ·  FSC 5925
NO DASHES 5925008165263
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

36 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
MATTMATERIALCASE PLASTIC
CQJXNOMINAL THREAD SIZEINCHES 0.138
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 208.0
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES MINIMUM 1.802 AND INCHES MAXIMUM 1.822
AEHADISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES MINIMUM 0.740 AND INCHES MAXIMUM 0.760
TTQYTERMINAL TYPE AND QUANTITYSCREW 4
CPRXACTUATOR POSITION DESIGNATIONAT EACH POLE
AKPXPOLE QUANTITY2
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 4
CPRYEXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE AND TWO LINKED
CPSMINTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
AAQLBODY STYLE
ABXDBUSHING LENGTHINCHES MINIMUM 0.120 AND INCHES MAXIMUM 0.140
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 3.000 AND MAXIMUM AT 200 PCT 9.000
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDDUSTPROOF
FREQFREQUENCY IN HERTZ400.0
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
CMLPTHREAD QUANTITY PER INCH32
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS MILLIAMPERES AC 100.0
ADATBODY WIDTHINCHES MINIMUM 1.490 AND INCHES MAXIMUM 1.510
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES MINIMUM 1.190 AND INCHES MAXIMUM 1.210
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
AFJNFRAGILITY FACTORMODERATELY RUGGED
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES MINIMUM 1.990 AND INCHES MAXIMUM 2.010
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 2
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 3500.0
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
CPRJTRIP RELEASE METHODALL LOCATIONS MAGNETIC-HYDRAULIC
ADAQBODY LENGTHINCHES MINIMUM 2.490 AND INCHES MAXIMUM 2.510
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT150.0
CPRQRESET METHODMANUAL
THSDTHREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES MINIMUM 0.740 AND INCHES MAXIMUM 0.760

Cross-references

5 manufacturer part numbers on file for this NSN — each shown against the CAGE code it belongs to.

Manufacturer cross-reference part numbers and CAGE codes
Manufacturer part numberCAGE
PCB837PT2XAM1774193
PCB837PT2XAM17CURVE5574193
2XAM17-01AMP208VAC400CPSTDC5574193
DMS 83059B16236
919559118876