Home / MS parts / NSN 5925-00-827-4942
NSN 5925-00-827-4942  ·  NIIN 008274942  ·  FSC 5925
NO DASHES 5925008274942
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

37 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 1.031
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
BBRJSPECIAL HANDLING FEATUREMAGNETIC
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 4
TTQYTERMINAL TYPE AND QUANTITYTHREADED STUD 4
AAQLBODY STYLE
FREQFREQUENCY IN HERTZ60.0
MATTMATERIALCASE PLASTIC
CPRXACTUATOR POSITION DESIGNATIONAT EACH POLE
CTJSUNPACKAGED UNIT WEIGHTPOUNDS NOMINAL 1.200
CMLPTHREAD QUANTITY PER INCH32
THSDTHREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 2
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
CPRJTRIP RELEASE METHODALL LOCATIONS MAGNETIC-HYDRAULIC
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
ADAQBODY LENGTHINCHES NOMINAL 2.031
ADATBODY WIDTHINCHES NOMINAL 2.031
CPRYEXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE AND TWO LINKED
CPSMINTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
CQJXNOMINAL THREAD SIZEINCHES 0.138
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 15.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 250.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 1500.0
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 1.031
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES NOMINAL 2.750
AEHADISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES NOMINAL 1.031
AFJNFRAGILITY FACTORMODERATELY RUGGED
AJECBOSS HEIGHTINCHES NOMINAL 0.156
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES MINIMUM 3.177 AND INCHES MAXIMUM 3.301
AKPXPOLE QUANTITY2
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 20.000 AND MAXIMUM AT 200 PCT 100.000
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDHUMIDITY RESISTANT AND VIBRATION RESISTANT AND SHOCK RESISTANT AND EXPLOSION PROOF AND SALT SPRAY PROOF AND FUNGUS RESISTANT AND SAND RESISTANT AND DUSTPROOF
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRQRESET METHODMANUAL

Cross-references

5 manufacturer part numbers on file for this NSN — each shown against the CAGE code it belongs to.

Manufacturer cross-reference part numbers and CAGE codes
Manufacturer part numberCAGE
2XAM1516-1574193
2XAM1516-15-125-1-6074193
2XAM1516-15-250VAC60C174193
410055-380020
2210+899699