Home / MS parts / NSN 5925-00-833-5227
NSN 5925-00-833-5227  ·  NIIN 008335227  ·  FSC 5925
NO DASHES 5925008335227
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

34 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
AFJNFRAGILITY FACTORMODERATELY RUGGED
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 2
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 1.938
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONAT POLE ONE
CPSMINTERNAL TRIP RELEASE CONFIGURATIONSINGLE LOCATION SERIES TRIP
CQJXNOMINAL THREAD SIZEINCHES 0.138
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTSINGLE LOCATION MINIMUM AT 150 PCT 10.000 AND MAXIMUM AT 150 PCT 30.000 AND MINIMUM AT 200 PCT 4.000 AND MAXIMUM AT 200 PCT 10.000 AND MINIMUM AT 300 PCT 1.400 AND MAXIMUM AT 300 PCT 4.000
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDEXPLOSION RESISTANT AND FUNGUS RESISTANT AND MOISTURE RESISTANT
CTJSUNPACKAGED UNIT WEIGHTOUNCES NOMINAL 4.250
FREQFREQUENCY IN HERTZ60.0
MATTMATERIALCASE PLASTIC
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES NOMINAL 2.611
AKPXPOLE QUANTITY1
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
AAQLBODY STYLE
ADAQBODY LENGTHINCHES NOMINAL 2.500
BBRJSPECIAL HANDLING FEATUREMAGNETIC
CMLPTHREAD QUANTITY PER INCH32
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLESINGLE LOCATION AMPERES AC 20.0
ADATBODY WIDTHINCHES NOMINAL 0.750
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES NOMINAL 1.812
CPRJTRIP RELEASE METHODSINGLE LOCATION MAGNETIC-HYDRAULIC
CPRLTRIP RELEASE CHARACTERISTICSINGLE LOCATION TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
CPRQRESET METHODMANUAL
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSSINGLE LOCATION AC 2000.0
CPRHCIRCUIT PROTECTION TYPESINGLE LOCATION OVERCURRENT
TTQYTERMINAL TYPE AND QUANTITYTHREADED STUD 2
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSSINGLE LOCATION AC 120.0
THSDTHREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)

Cross-references

3 manufacturer part numbers on file for this NSN — each shown against the CAGE code it belongs to.

Manufacturer cross-reference part numbers and CAGE codes
Manufacturer part numberCAGE
AM13MG3-20AMP120VACTDC474193
AM13MG3-20-120-4-6074193
1035164918876