Home / MS parts / NSN 5925-00-839-4567
NSN 5925-00-839-4567  ·  NIIN 008394567  ·  FSC 5925
NO DASHES 5925008394567
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

38 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND MOISTURE RESISTANT
CQJXNOMINAL THREAD SIZEINCHES 0.138
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
AEHADISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES MINIMUM 1.021 AND INCHES MAXIMUM 1.041
AFJNFRAGILITY FACTORMODERATELY RUGGED
AJECBOSS HEIGHTINCHES MINIMUM 0.146 AND INCHES MAXIMUM 0.166
FREQFREQUENCY IN HERTZ400.0
CPRQRESET METHODMANUAL
CPRYEXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 10.000 AND MAXIMUM AT 200 PCT 30.000
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT150.0
CPRPULTIMATE TRIP TIME PER POLE IN SECONDSALL LOCATIONS NOMINAL 150.000
CPRXACTUATOR POSITION DESIGNATIONAT EACH POLE
TTQYTERMINAL TYPE AND QUANTITYTHREADED STUD 6
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES NOMINAL 3.239
AKPXPOLE QUANTITY3
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 6
AAQLBODY STYLE
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES MINIMUM 3.053 AND INCHES MAXIMUM 3.073
MATTMATERIALCASE PLASTIC
THSDTHREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
CPRJTRIP RELEASE METHODALL LOCATIONS MAGNETIC
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
BBRJSPECIAL HANDLING FEATUREMAGNETIC
CMLPTHREAD QUANTITY PER INCH32
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 32.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 416.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 1500.0
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
ADAQBODY LENGTHINCHES MINIMUM 3.709 AND INCHES MAXIMUM 3.729
ADATBODY WIDTHINCHES MINIMUM 3.042 AND INCHES MAXIMUM 3.062
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 3
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES MINIMUM 1.021 AND INCHES MAXIMUM 1.041
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES MINIMUM 2.740 AND INCHES MAXIMUM 2.760
CPRWACTUATOR FUNCTIONTRIP-RESET
CPSMINTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP

Cross-references

4 manufacturer part numbers on file for this NSN — each shown against the CAGE code it belongs to.

Manufacturer cross-reference part numbers and CAGE codes
Manufacturer part numberCAGE
3XAM1516MG3-32AMP416VAC1174193
53-161-6-MG374193
53-161MG3 32 416VAC1-400HZ74193
9169283-118876