NSN 5925-00-932-0038 · NIIN 009320038 · FSC 5925
NO DASHES 5925009320038
In Stock
CIRCUIT BREAKER
Circuit Breakers
Technical characteristics
32 rows
Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.
| MRC | Requirement | Value |
|---|---|---|
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | SINGLE LOCATION AMPERES DC 150.0 |
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | SINGLE LOCATION DC 575.0 |
| CPRH | CIRCUIT PROTECTION TYPE | SINGLE LOCATION OVERCURRENT |
| CPRJ | TRIP RELEASE METHOD | SINGLE LOCATION THERMAL |
| CPRL | TRIP RELEASE CHARACTERISTIC | SINGLE LOCATION TIME DELAY |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 138.0 |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | THREADED HOLE(S) 2 |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| ADAT | BODY WIDTH | INCHES NOMINAL 1.875 |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SINGLE LOCATION SERIES TRIP |
| CQJX | NOMINAL THREAD SIZE | INCHES 0.190 |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | SINGLE LOCATION MINIMUM AT 200 PCT 8.000 AND MAXIMUM AT 200 PCT 50.000 |
| CRCF | TRIP RELEASE AMBIENT TEMP RATING | SINGLE LOCATION CELSIUS NOMINAL 25.0 |
| MATT | MATERIAL | CASE PLASTIC |
| TEST | TEST DATA DOCUMENT | SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.). 81349--IL-C-13516 |
| THSD | THREAD SERIES DESIGNATOR | UNF |
| TTQY | TERMINAL TYPE AND QUANTITY | THREADED STUD 2 |
| ZZZK | SPECIFICATION/STANDARD DATA | GOVERNMENT SPECIFICATION 81349--13516 TO 4 |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | INCHES NOMINAL 1.063 |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | INCHES NOMINAL 2.406 |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | SINGLE LOCATION DC 28.0 |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | PUSH BUTTON 1 |
| AAQL | BODY STYLE | |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | INCHES MAXIMUM 1.625 |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| ABHP | OVERALL LENGTH | INCHES NOMINAL 3.227 |
| AKPX | POLE QUANTITY | 1 |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
| CMLP | THREAD QUANTITY PER INCH | 32 |
Cross-references
11 manufacturer part numbers on file for this NSN — each shown against the CAGE code it belongs to.
| Manufacturer part number | CAGE |
|---|---|
| A14313 | 47362 |
| 51771 | 53397 |
| S19745 | 80072 |
| M13516/4-12 | 81349 |
| M13516/4BI-150 | 81349 |
| MIL-C-13516/4 | 81349 |
| PDLM-150 | 82647 |
| MS39065+6 | 96906 |
| JHP13-330 | 02032 |
| 870SS0046 | 0291H |
| B243858AB | 10001 |
Supersedes
This item replaces cancelled NIIN 002270393. An older drawing citing one of those numbers resolves here.