NSN 5925-01-011-9230 · NIIN 010119230 · FSC 5925
NO DASHES 5925010119230
In Stock
CIRCUIT BREAKER
Circuit Breakers
Technical characteristics
37 rows
Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.
| MRC | Requirement | Value |
|---|---|---|
| AAQL | BODY STYLE | |
| ABXD | BUSHING LENGTH | INCHES MAXIMUM 0.380 |
| ADAQ | BODY LENGTH | INCHES MAXIMUM 1.562 |
| ADAT | BODY WIDTH | INCHES MAXIMUM 1.937 |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | INCHES MINIMUM 0.844 AND INCHES MAXIMUM 0.906 |
| AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | INCHES MINIMUM 0.594 AND INCHES MAXIMUM 0.656 |
| AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | INCHES MAXIMUM 1.780 |
| AKPX | POLE QUANTITY | 3 |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | THREADED BUSHING WITH PANEL SEAL 1 |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
| CMLP | THREAD QUANTITY PER INCH | 32 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | FIRST LOCATION MILLIAMPERES AC 500.0 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | SECOND LOCATION AMPERES AC 5.0 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | THIRD LOCATION AMPERES AC 2.0 |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | ALL LOCATIONS AC 250.0 |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | ALL LOCATIONS AC 1000.0 |
| CPRH | CIRCUIT PROTECTION TYPE | ALL LOCATIONS OVERCURRENT |
| CPRJ | TRIP RELEASE METHOD | ALL LOCATIONS MAGNETIC-HYDRAULIC |
| CPRL | TRIP RELEASE CHARACTERISTIC | ALL LOCATIONS TIME DELAY |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 115.0 |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | TOGGLE 1 |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | FIRST LOCATION RELAY TRIP |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | THIRD LOCATION SERIES TRIP |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SECOND LOCATION SERIES TRIP |
| CQJX | NOMINAL THREAD SIZE | INCHES 0.375 |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | ALL LOCATIONS MINIMUM AT 200 PCT 0.070 AND MAXIMUM AT 200 PCT 0.700 |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND MOISTURE RESISTANT AND HERMETICALLY SEALED |
| CTJS | UNPACKAGED UNIT WEIGHT | OUNCES NOMINAL 5.400 |
| FREQ | FREQUENCY IN HERTZ | 400.0 |
| THSD | THREAD SERIES DESIGNATOR | UNEF |
| TTQY | TERMINAL TYPE AND QUANTITY | WIRE HOOK 6 |
Cross-references
4 manufacturer part numbers on file for this NSN — each shown against the CAGE code it belongs to.
| Manufacturer part number | CAGE |
|---|---|
| 9999-9300 | 50027 |
| AP411-3016-1 | 81541 |
| AP411 | 81541 |
| 47127 | 98853 |