NSN 5925-01-043-5811 · NIIN 010435811 · FSC 5925
NO DASHES 5925010435811
In Stock
CIRCUIT BREAKER
Circuit Breakers
Technical characteristics
32 rows
Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.
| MRC | Requirement | Value |
|---|---|---|
| AAQL | BODY STYLE | |
| ADAQ | BODY LENGTH | INCHES NOMINAL 11.000 |
| ADAT | BODY WIDTH | INCHES NOMINAL 6.000 |
| ADAU | BODY HEIGHT | INCHES NOMINAL 4.062 |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | INCHES NOMINAL 9.250 |
| AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | INCHES NOMINAL 2.000 |
| AEBV | UNTHREADED MOUNTING HOLE DIAMETER | INCHES NOMINAL 0.216 |
| AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | INCHES NOMINAL 9.250 |
| AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | INCHES NOMINAL 2.000 |
| AJEC | BOSS HEIGHT | INCHES NOMINAL 0.219 |
| AKPX | POLE QUANTITY | 2 |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | UNTHREADED HOLE(S) 4 |
| BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
| CBBL | FEATURES PROVIDED | ADJUSTABLE TRIP RELEASE |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | ALL LOCATIONS AMPERES AC 400.0 AND AMPERES DC 400.0 |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | ALL LOCATIONS AC 600.0 AND DC 250.0 |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | ALL LOCATIONS AC 22000.0 AND DC 10000.0 |
| CPRH | CIRCUIT PROTECTION TYPE | ALL LOCATIONS OVERCURRENT |
| CPRJ | TRIP RELEASE METHOD | ALL LOCATIONS THERMAL-MAGNETIC |
| CPRL | TRIP RELEASE CHARACTERISTIC | ALL LOCATIONS INSTANTANEOUS |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 145.0 |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | TOGGLE 1 |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | BETWEEN POLE ONE AND TWO |
| CPSF | ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS | ALL LOCATIONS AC 2000.0 TO 4000.0 AND DC 2000.0 TO 4000.0 |
| CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF |
| CRCF | TRIP RELEASE AMBIENT TEMP RATING | ALL LOCATIONS CELSIUS NOMINAL 40.0 |
| FREQ | FREQUENCY IN HERTZ | 60.0 |
| MATT | MATERIAL | CASE PLASTIC |
| TTQY | TERMINAL TYPE AND QUANTITY | COMPRESSION 4 |
Cross-references
4 manufacturer part numbers on file for this NSN — each shown against the CAGE code it belongs to.
| Manufacturer part number | CAGE |
|---|---|
| LA 26400 AB | 56365 |
| LA 26400 AB | 88434 |
| LA-26400 (A OR B OR C) | 88434 |
| LA-26400 | 88434 |