Home / MS parts / NSN 5925-01-063-4380
NSN 5925-01-063-4380  ·  NIIN 010634380  ·  FSC 5925
NO DASHES 5925010634380
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

41 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
AAQLBODY STYLE
ABXDBUSHING LENGTHINCHES MINIMUM 0.332 AND INCHES MAXIMUM 0.380
ADAQBODY LENGTHINCHES MAXIMUM 1.500
ADATBODY WIDTHINCHES MAXIMUM 1.250
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES MINIMUM 0.594 AND INCHES MAXIMUM 0.656
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES MINIMUM 0.344 AND INCHES MAXIMUM 0.406
AEFSNONTURN DEVICE DIAMETERINCHES NOMINAL 0.250
AFJNFRAGILITY FACTORMODERATELY RUGGED
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES MAXIMUM 1.780
AKPXPOLE QUANTITY2
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED BUSHING WITH PANEL SEAL 1
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
BBRJSPECIAL HANDLING FEATUREMAGNETIC
CMLPTHREAD QUANTITY PER INCH32
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLESECOND LOCATION AMPERES AC 20.0
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEFIRST LOCATION AMPERES DC 10.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSSECOND LOCATION AC 240.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSFIRST LOCATION DC 50.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSFIRST LOCATION DC 500.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSSECOND LOCATION AC 1000.0
CPRHCIRCUIT PROTECTION TYPEFIRST LOCATION OVERVOLTAGE
CPRHCIRCUIT PROTECTION TYPESECOND LOCATION OVERCURRENT
CPRJTRIP RELEASE METHODALL LOCATIONS MAGNETIC
CPRLTRIP RELEASE CHARACTERISTICFIRST LOCATION INSTANTANEOUS
CPRLTRIP RELEASE CHARACTERISTICSECOND LOCATION TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT120.0
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONBETWEEN POLE ONE AND TWO
CPSMINTERNAL TRIP RELEASE CONFIGURATIONFIRST LOCATION SERIES TRIP
CPSMINTERNAL TRIP RELEASE CONFIGURATIONSECOND LOCATION RELAY TRIP
CQJXNOMINAL THREAD SIZEINCHES 0.375
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTSECOND LOCATION MINIMUM AT 200 PCT 0.100 AND MAXIMUM AT 200 PCT 0.700
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDHERMETICALLY SEALED AND SHOCKPROOF AND VIBRATIONPROOF
CTJSUNPACKAGED UNIT WEIGHTOUNCES NOMINAL 3.600
FREQFREQUENCY IN HERTZ60.0
THSDTHREAD SERIES DESIGNATORUNEF
TTQYTERMINAL TYPE AND QUANTITYWIRE HOOK 5

Cross-references

6 manufacturer part numbers on file for this NSN — each shown against the CAGE code it belongs to.

Manufacturer cross-reference part numbers and CAGE codes
Manufacturer part numberCAGE
V45DC20ESM3630992
V45DC20EHE2A30992
1314479-170143
V45DC20EHE2A80058
AP41-7323-181541
AP41-4698-281541

Supersedes

This item replaces cancelled NIIN 010251650. An older drawing citing one of those numbers resolves here.