Home / MS parts / NSN 5925-01-090-8336
NSN 5925-01-090-8336  ·  NIIN 010908336  ·  FSC 5925
NO DASHES 5925010908336
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

34 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
AAQLBODY STYLE
ADAQBODY LENGTHINCHES MINIMUM 2.490 AND INCHES MAXIMUM 2.510
ADATBODY WIDTHINCHES MINIMUM 0.740 AND INCHES MAXIMUM 0.760
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES MINIMUM 1.928 AND INCHES MAXIMUM 1.948
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES MINIMUM 2.052 AND INCHES MAXIMUM 2.072
AFJNFRAGILITY FACTORMODERATELY RUGGED
AJECBOSS HEIGHTINCHES MINIMUM 0.130 AND INCHES MAXIMUM 0.150
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES NOMINAL 2.611
AKPXPOLE QUANTITY1
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 2
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
CMLPTHREAD QUANTITY PER INCH32
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLESINGLE LOCATION AMPERES AC 12.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSSINGLE LOCATION AC 240.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSSINGLE LOCATION AC 5000.0
CPRHCIRCUIT PROTECTION TYPESINGLE LOCATION OVERCURRENT
CPRJTRIP RELEASE METHODSINGLE LOCATION MAGNETIC-HYDRAULIC
CPRLTRIP RELEASE CHARACTERISTICSINGLE LOCATION TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
CPRPULTIMATE TRIP TIME PER POLE IN SECONDSSINGLE LOCATION MINIMUM 1.000 AND MAXIMUM 6.000
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
CPRWACTUATOR FUNCTIONTRIP W/SEPARATE RESET
CPRXACTUATOR POSITION DESIGNATIONAT POLE ONE
CPSMINTERNAL TRIP RELEASE CONFIGURATIONSINGLE LOCATION SERIES TRIP
CQJXNOMINAL THREAD SIZEINCHES 0.138
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTSINGLE LOCATION MINIMUM AT 200 PCT 2.000 AND MAXIMUM AT 200 PCT 20.000 AND MINIMUM AT 400 PCT 0.300 AND MAXIMUM AT 400 PCT 2.000 AND MINIMUM AT 1000 PCT 0.003 AND MAXIMUM AT 1000 PCT 0.040
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDDUSTPROOF AND FUNGUS PROOF
FREQFREQUENCY IN HERTZ60.0
MATTMATERIALCASE PLASTIC
THSDTHREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
TTQYTERMINAL TYPE AND QUANTITYTHREADED STUD 2

Cross-references

4 manufacturer part numbers on file for this NSN — each shown against the CAGE code it belongs to.

Manufacturer cross-reference part numbers and CAGE codes
Manufacturer part numberCAGE
264-200007-00320886
AM1-A3-A-12-274193
W91X11-2-1277342
UPL-1-1-6-2-12381541