Home / MS parts / NSN 5925-01-111-9949
NSN 5925-01-111-9949  ·  NIIN 011119949  ·  FSC 5925
NO DASHES 5925011119949
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

40 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
AAQLBODY STYLE
ADAQBODY LENGTHINCHES MINIMUM 2.490 AND INCHES MAXIMUM 2.510
ADATBODY WIDTHINCHES MINIMUM 2.990 AND INCHES MAXIMUM 3.010
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES MINIMUM 1.928 AND INCHES MAXIMUM 1.948
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES MINIMUM 0.740 AND INCHES MAXIMUM 0.760
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES MINIMUM 2.052 AND INCHES MAXIMUM 2.062
AEHADISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES MINIMUM 0.740 AND INCHES MAXIMUM 0.760
AFJNFRAGILITY FACTORMODERATELY RUGGED
AJECBOSS HEIGHTINCHES MINIMUM 0.130 AND INCHES MAXIMUM 0.150
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES MINIMUM 2.461 AND INCHES MAXIMUM 2.481
AKPXPOLE QUANTITY4
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 8
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
CBBLFEATURES PROVIDEDSLIDING BAR INTERLOCK
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 30.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 240.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 5000.0
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
CPRJTRIP RELEASE METHODALL LOCATIONS MAGNETIC-HYDRAULIC
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
CPRPULTIMATE TRIP TIME PER POLE IN SECONDSALL LOCATIONS MINIMUM 0.700
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 4
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONAT EACH POLE
CPRYEXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, THREE, AND FOUR LINKED
CPSMINTERNAL TRIP RELEASE CONFIGURATIONTHIRD LOCATION SERIES TRIP
CPSMINTERNAL TRIP RELEASE CONFIGURATIONFIRST LOCATION RELAY TRIP
CPSMINTERNAL TRIP RELEASE CONFIGURATIONSECOND LOCATION SERIES TRIP
CPSMINTERNAL TRIP RELEASE CONFIGURATIONFOURTH LOCATION SERIES TRIP
CQJXNOMINAL THREAD SIZEINCHES 0.138
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 0.180 AND MAXIMUM AT 200 PCT 1.800
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND MOISTURE RESISTANT
FREQFREQUENCY IN HERTZ50.0 OR 60.0
MATTMATERIALCASE PLASTIC
THSDTHREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
TTQYTERMINAL TYPE AND QUANTITYTHREADED STUD 10

Cross-references

3 manufacturer part numbers on file for this NSN — each shown against the CAGE code it belongs to.

Manufacturer cross-reference part numbers and CAGE codes
Manufacturer part numberCAGE
AM4-A6A3A3A3-A-30-250-374193
AM4-A6-A3-A3-A3-A-30-374193
37675402-00108783