Home / MS parts / NSN 5925-01-123-2828
NSN 5925-01-123-2828  ·  NIIN 011232828  ·  FSC 5925
NO DASHES 5925011232828
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

37 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
AAQLBODY STYLE
ADAQBODY LENGTHINCHES MAXIMUM 15.500
ADATBODY WIDTHINCHES MAXIMUM 9.000
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 12.750
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 3.000
AEBVUNTHREADED MOUNTING HOLE DIAMETERINCHES NOMINAL 0.250
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES NOMINAL 14.625
AEGJSWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
AEHADISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES NOMINAL 3.000
AJECBOSS HEIGHTINCHES NOMINAL 0.125
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES NOMINAL 10.375
AKPXPOLE QUANTITY3
AXHRMOUNTING FACILITY TYPE AND QUANTITYUNTHREADED HOLE(S) 4
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 400.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 500.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 100000.0
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
CPRJTRIP RELEASE METHODALL LOCATIONS THERMAL-MAGNETIC
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS INSTANTANEOUS AND TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT140.0
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONAT POLE TWO
CPRZAUXILIARY SWITCH FUNCTION AND QUANTITYALARM 1
CQSMSWITCH LOCATION AND POSITION DESIGNATIONINTERNAL AT POLE THREE
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 20.000 AND MAXIMUM AT 200 PCT 32.000
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDGENERAL PURPOSE
CRCFTRIP RELEASE AMBIENT TEMP RATINGALL LOCATIONS CELSIUS NOMINAL 50.0
CRTKSWITCH TERMINAL TYPETAB, SOLDER LUG
CSSXSWITCH CURRENT RATING AND TYPE IN AMPSAC 5.0 AND DC 5.0
CSWPSWITCH VOLTAGE RATING AND TYPE IN VOLTSAC 250.0 AND DC 30.0
FREQFREQUENCY IN HERTZ60.0
MATTMATERIALCASE PLASTIC
TTQYTERMINAL TYPE AND QUANTITYTHREADED STUD 6

Cross-references

5 manufacturer part numbers on file for this NSN — each shown against the CAGE code it belongs to.

Manufacturer cross-reference part numbers and CAGE codes
Manufacturer part numberCAGE
ETN6909-10S3130086
ETN6909-10S3131955
1241C54G013D982
1241C54G014N509
1241C54G0189946