NSN 5925-01-133-8449 · NIIN 011338449 · FSC 5925
NO DASHES 5925011338449
In Stock
CIRCUIT BREAKER
Circuit Breakers
Technical characteristics
30 rows
Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.
| MRC | Requirement | Value |
|---|---|---|
| AAQL | BODY STYLE | |
| ABXD | BUSHING LENGTH | INCHES MINIMUM 0.332 AND INCHES MAXIMUM 0.380 |
| ADAQ | BODY LENGTH | INCHES MAXIMUM 1.937 |
| ADAT | BODY WIDTH | INCHES MAXIMUM 1.562 |
| AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | INCHES MAXIMUM 0.906 |
| AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | INCHES NOMINAL 0.625 |
| AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | INCHES MAXIMUM 1.828 |
| AKPX | POLE QUANTITY | 3 |
| AXHR | MOUNTING FACILITY TYPE AND QUANTITY | THREADED BUSHING WITH PANEL SEAL 2 |
| CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | ALL LOCATIONS AMPERES AC 20.0 |
| CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | ALL LOCATIONS AC 120.0 |
| CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | ALL LOCATIONS AC 300.0 |
| CPRH | CIRCUIT PROTECTION TYPE | ALL LOCATIONS OVERCURRENT |
| CPRJ | TRIP RELEASE METHOD | ALL LOCATIONS MAGNETIC-HYDRAULIC |
| CPRL | TRIP RELEASE CHARACTERISTIC | ALL LOCATIONS TIME DELAY |
| CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 135.0 |
| CPRP | ULTIMATE TRIP TIME PER POLE IN SECONDS | ALL LOCATIONS MINIMUM 3.000 AND MAXIMUM 60.000 |
| CPRQ | RESET METHOD | MANUAL |
| CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | TOGGLE 1 |
| CPRW | ACTUATOR FUNCTION | TRIP-RESET |
| CPRX | ACTUATOR POSITION DESIGNATION | AT EACH POLE |
| CPRY | EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
| CPSM | INTERNAL TRIP RELEASE CONFIGURATION | ALL LOCATIONS SERIES TRIP |
| CQJX | NOMINAL THREAD SIZE | INCHES 0.380 |
| CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | ALL LOCATIONS MINIMUM AT 135 PCT 3.000 AND MAXIMUM AT 135 PCT 60.000 AND MINIMUM AT 200 PCT 0.500 AND MAXIMUM AT 200 PCT 9.000 AND MAXIMUM AT 400 PCT 1.750 AND MAXIMUM AT 600 PCT 0.600 AND MAXIMUM AT 800 PCT 0.100 |
| FREQ | FREQUENCY IN HERTZ | 60.0 OR 400.0 |
| MATT | MATERIAL | CASE PORCELAIN |
| THSD | THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |
| TTQY | TERMINAL TYPE AND QUANTITY | WIRE HOOK 3 |