Home / MS parts / NSN 5925-01-159-6595
NSN 5925-01-159-6595  ·  NIIN 011596595  ·  FSC 5925
NO DASHES 5925011596595
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

56 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
AAQLBODY STYLE
ADAQBODY LENGTHINCHES MINIMUM 2.490 AND INCHES MAXIMUM 2.510
ADATBODY WIDTHINCHES MINIMUM 2.990 AND INCHES MAXIMUM 3.010
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES MINIMUM 1.928 AND INCHES MAXIMUM 1.948
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES MINIMUM 0.740 AND INCHES MAXIMUM 0.760
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES MINIMUM 2.052 AND INCHES MAXIMUM 2.072
AEHADISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES MINIMUM 0.740 AND INCHES MAXIMUM 0.760
AFJNFRAGILITY FACTORMODERATELY RUGGED
AJECBOSS HEIGHTINCHES MINIMUM 0.140 AND INCHES MAXIMUM 0.150
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES MINIMUM 2.461 AND INCHES MAXIMUM 2.481
AKPXPOLE QUANTITY4
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 8
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
BBRJSPECIAL HANDLING FEATUREMAGNETIC
CMLPTHREAD QUANTITY PER INCH32
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLETHIRD LOCATION AMPERES AC 10.0
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEFIRST LOCATION AMPERES AC 10.0
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLESECOND LOCATION AMPERES AC 10.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSFIRST LOCATION AC 240.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSSECOND LOCATION AC 240.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSFOURTH LOCATION DC 20.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSTHIRD LOCATION AC 240.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSFIRST LOCATION AC 1000.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSTHIRD LOCATION AC 1000.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSSECOND LOCATION AC 1000.0
CPRHCIRCUIT PROTECTION TYPEFIRST LOCATION OVERCURRENT
CPRHCIRCUIT PROTECTION TYPEFOURTH LOCATION UNDERVOLTAGE
CPRHCIRCUIT PROTECTION TYPESECOND LOCATION OVERCURRENT
CPRHCIRCUIT PROTECTION TYPETHIRD LOCATION OVERCURRENT
CPRJTRIP RELEASE METHODTHIRD LOCATION MAGNETIC-HYDRAULIC
CPRJTRIP RELEASE METHODFIRST LOCATION MAGNETIC-HYDRAULIC
CPRJTRIP RELEASE METHODSECOND LOCATION MAGNETIC-HYDRAULIC
CPRLTRIP RELEASE CHARACTERISTICSECOND LOCATION TIME DELAY
CPRLTRIP RELEASE CHARACTERISTICFIRST LOCATION TIME DELAY
CPRLTRIP RELEASE CHARACTERISTICTHIRD LOCATION TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 4
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONAT EACH POLE
CPRYEXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, THREE, AND FOUR LINKED
CPSMINTERNAL TRIP RELEASE CONFIGURATIONSECOND LOCATION SERIES TRIP
CPSMINTERNAL TRIP RELEASE CONFIGURATIONTHIRD LOCATION SERIES TRIP
CPSMINTERNAL TRIP RELEASE CONFIGURATIONFIRST LOCATION SERIES TRIP
CQJXNOMINAL THREAD SIZEINCHES 0.138
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTSECOND LOCATION MINIMUM AT 200 PCT 2.000 AND MAXIMUM AT 200 PCT 20.000
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTFIRST LOCATION MINIMUM AT 200 PCT 2.000 AND MAXIMUM AT 200 PCT 20.000
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTTHIRD LOCATION MINIMUM AT 200 PCT 2.000 AND MAXIMUM AT 200 PCT 20.000
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND MOISTURE RESISTANT
CTJSUNPACKAGED UNIT WEIGHTOUNCES NOMINAL 12.500
FREQFREQUENCY IN HERTZ50.0 OR 400.0
MATTMATERIALCASE PLASTIC
THSDTHREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
TTQYTERMINAL TYPE AND QUANTITYTHREADED STUD 8

Cross-references

6 manufacturer part numbers on file for this NSN — each shown against the CAGE code it belongs to.

Manufacturer cross-reference part numbers and CAGE codes
Manufacturer part numberCAGE
996302-53B150
996302-549956
996302-554X10
AM4-Z68-574193
AM4S-Z1001-1WL3330
AM4-Z68-5L3330