Home / MS parts / NSN 5925-01-174-0335
NSN 5925-01-174-0335  ·  NIIN 011740335  ·  FSC 5925
NO DASHES 5925011740335
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

36 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
AAQLBODY STYLE
ABXDBUSHING LENGTHINCHES MINIMUM 0.332 AND INCHES MAXIMUM 0.380
ADAQBODY LENGTHINCHES MAXIMUM 1.562
ADATBODY WIDTHINCHES MAXIMUM 1.281
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES MAXIMUM 0.906
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 0.625
AEFSNONTURN DEVICE DIAMETERINCHES NOMINAL 0.250
AFJNFRAGILITY FACTORMODERATELY RUGGED
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES MAXIMUM 1.950
AKPXPOLE QUANTITY2
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED BUSHING WITH PANEL SEAL 1
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
BBRJSPECIAL HANDLING FEATUREMAGNETIC
CBBLFEATURES PROVIDEDHIGH INRUSH PROTECTION
CMLPTHREAD QUANTITY PER INCH32
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 5.0 AND AMPERES DC 5.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 240.0 AND DC 50.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 500.0 AND DC 500.0
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
CPRJTRIP RELEASE METHODALL LOCATIONS MAGNETIC
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT115.0
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONBETWEEN POLE ONE AND TWO
CPSMINTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
CQJXNOMINAL THREAD SIZEINCHES 0.375
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 0.500 AND MAXIMUM AT 200 PCT 9.000
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND SHOCK RESISTANT AND MOISTURE RESISTANT AND SALT SPRAY PROOF AND VIBRATION RESISTANT
CTJSUNPACKAGED UNIT WEIGHTGRAMS NOMINAL 100.0
FREQFREQUENCY IN HERTZ60.0
THSDTHREAD SERIES DESIGNATORUNEF
TTQYTERMINAL TYPE AND QUANTITYTAB W/SCREW 4

Cross-references

3 manufacturer part numbers on file for this NSN — each shown against the CAGE code it belongs to.

Manufacturer cross-reference part numbers and CAGE codes
Manufacturer part numberCAGE
AP167063-23181541
AP16-7063-23182647
MIS-31509-23118876