MRCRequirementValue
AAQLBODY STYLE
ADAQBODY LENGTHINCHES MINIMUM 1.985 AND INCHES MAXIMUM 2.015
ADATBODY WIDTHINCHES MINIMUM 1.468 AND INCHES MAXIMUM 1.532
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES MINIMUM 1.555 AND INCHES MAXIMUM 1.565
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES MINIMUM 0.745 AND INCHES MAXIMUM 0.755
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES MINIMUM 1.655 AND INCHES MAXIMUM 1.665
AEGJSWITCH CONTACT ARRANGEMENTDOUBLE POLE, DOUBLE THROW
AEHADISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES MINIMUM 0.745 AND INCHES MAXIMUM 0.755
AFJNFRAGILITY FACTORMODERATELY RUGGED
AJECBOSS HEIGHTINCHES MINIMUM 0.125 AND INCHES MAXIMUM 0.135
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES MINIMUM 1.898 AND INCHES MAXIMUM 1.962
AKPXPOLE QUANTITY2
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 4
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
CMLPTHREAD QUANTITY PER INCH32
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 25.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 250.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 1000.0
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
CPRJTRIP RELEASE METHODALL LOCATIONS MAGNETIC-HYDRAULIC
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 2
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONAT EACH POLE
CPRYEXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE AND TWO LINKED
CPRZAUXILIARY SWITCH FUNCTION AND QUANTITYALARM 2
CPSMINTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
CQJXNOMINAL THREAD SIZEINCHES 0.138
CQSMSWITCH LOCATION AND POSITION DESIGNATIONINTERNAL AT EACH POLE
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 2.000 AND MAXIMUM AT 200 PCT 20.000
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDDUSTPROOF AND FUNGUS PROOF
CRTKSWITCH TERMINAL TYPETAB, SOLDER LUG
CSSXSWITCH CURRENT RATING AND TYPE IN AMPSAC 0.5 AND DC 0.5
CSWPSWITCH VOLTAGE RATING AND TYPE IN VOLTSAC 120.0 AND DC 50.0
FREQFREQUENCY IN HERTZ60.0
MATTMATERIALCASE PLASTIC
THSDTHREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
TTQYTERMINAL TYPE AND QUANTITYTAB, SOLDER LUG 4

Cross-references

3 manufacturer part numbers on file for this NSN — each shown against the CAGE code it belongs to.

Manufacturer cross-reference part numbers and CAGE codes
Manufacturer part numberCAGE
JA2-A14-A-25-274193
JA2-A14-A3-A-25-274193
UPGH-11-1REC2-62F-253-9081541