CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

39 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
AAQLBODY STYLE
ABKWOVERALL HEIGHTINCHES NOMINAL 11.063
ADAQBODY LENGTHINCHES NOMINAL 17.938
ADATBODY WIDTHINCHES NOMINAL 9.000
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 15.125
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 3.000
AEBVUNTHREADED MOUNTING HOLE DIAMETERINCHES NOMINAL 0.225
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES NOMINAL 17.000
AEGJSWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
AEHADISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES NOMINAL 3.000
AJECBOSS HEIGHTINCHES NOMINAL 0.250
AKPXPOLE QUANTITY3
AXHRMOUNTING FACILITY TYPE AND QUANTITYUNTHREADED HOLE(S) 4
CBBLFEATURES PROVIDEDADJUSTABLE TRIP RELEASE
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 350.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 500.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 100000.0
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
CPRJTRIP RELEASE METHODALL LOCATIONS THERMAL-MAGNETIC
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS INSTANTANEOUS AND TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONAT POLE TWO
CPRZAUXILIARY SWITCH FUNCTION AND QUANTITYALARM 1
CPSFADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPSALL LOCATIONS AC 1380.0 TO 2280.0
CQSMSWITCH LOCATION AND POSITION DESIGNATIONINTERNAL AT POLE THREE
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 600 PCT 20.000 AND MAXIMUM AT 600 PCT 32.000
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDGENERAL PURPOSE
CRCFTRIP RELEASE AMBIENT TEMP RATINGALL LOCATIONS CELSIUS NOMINAL 50.0
CRTKSWITCH TERMINAL TYPEWIRE LEAD
CSSXSWITCH CURRENT RATING AND TYPE IN AMPSAC 15.0 AND DC 0.5
CSWPSWITCH VOLTAGE RATING AND TYPE IN VOLTSAC 460.0 AND DC 125.0
FEATSPECIAL FEATURESSHUNT TRIP 450 VAC
FREQFREQUENCY IN HERTZ60.0
MATTMATERIALCASE PLASTIC
TTQYTERMINAL TYPE AND QUANTITYTHREADED STUD 6

Cross-references

3 manufacturer part numbers on file for this NSN — each shown against the CAGE code it belongs to.

Manufacturer cross-reference part numbers and CAGE codes
Manufacturer part numberCAGE
ETN690610S3630086
302-34-10758475
5925PL09917109009H