Home / MS parts / NSN 5925-01-332-5634
NSN 5925-01-332-5634  ·  NIIN 013325634  ·  FSC 5925
NO DASHES 5925013325634
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

37 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
AAQLBODY STYLE
ABTDMOUNTING SLOT WIDTHINCHES MINIMUM 0.154 AND INCHES MAXIMUM 0.174
ADAQBODY LENGTHINCHES MINIMUM 4.740 AND INCHES MAXIMUM 4.760
ADATBODY WIDTHINCHES MAXIMUM 2.072
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES MINIMUM 3.537 AND INCHES MAXIMUM 3.557
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES MINIMUM 1.016 AND INCHES MAXIMUM 1.036
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES MINIMUM 2.740 AND INCHES MAXIMUM 2.760
AEHADISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES MINIMUM 1.016 AND INCHES MAXIMUM 1.036
AFJNFRAGILITY FACTORMODERATELY RUGGED
AJECBOSS HEIGHTINCHES MINIMUM 0.209 AND INCHES MAXIMUM 0.229
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES MINIMUM 3.475 AND INCHES MAXIMUM 3.495
AKPXPOLE QUANTITY2
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 4 AND SLOT 2
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
BBRJSPECIAL HANDLING FEATUREMAGNETIC
CMLPTHREAD QUANTITY PER INCH32
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES DC 10.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS DC 140.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS DC 5000.0
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
CPRJTRIP RELEASE METHODALL LOCATIONS MAGNETIC
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 2
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONAT EACH POLE
CPRYEXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE AND TWO LINKED
CPSMINTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
CQJXNOMINAL THREAD SIZEINCHES 0.138
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 21.000 AND MAXIMUM AT 200 PCT 100.000
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDVIBRATION RESISTANT AND SHOCK RESISTANT AND MOISTURE RESISTANT AND SALT SPRAY PROOF
MATTMATERIALCASE PLASTIC
THSDTHREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
TTQYTERMINAL TYPE AND QUANTITYTHREADED STUD 4

Cross-references

3 manufacturer part numbers on file for this NSN — each shown against the CAGE code it belongs to.

Manufacturer cross-reference part numbers and CAGE codes
Manufacturer part numberCAGE
CD2-Z299-374193
841398-306481
841398-313973