Home / MS parts / NSN 5925-00-521-8208
NSN 5925-00-521-8208  ·  NIIN 005218208  ·  FSC 5925
NO DASHES 5925005218208
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

36 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
AAQLBODY STYLE
ADAQBODY LENGTHINCHES MINIMUM 2.490 AND INCHES MAXIMUM 2.510
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT150.0
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES MINIMUM 1.180 AND INCHES MAXIMUM 1.200
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES MINIMUM 0.740 AND INCHES MAXIMUM 0.760
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES MINIMUM 1.802 AND INCHES MAXIMUM 1.822
AEHADISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES MINIMUM 0.740 AND INCHES MAXIMUM 0.760
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDEXPLOSION RESISTANT
FREQFREQUENCY IN HERTZ480.0
MATTMATERIALCASE PLASTIC
THSDTHREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
TTQYTERMINAL TYPE AND QUANTITYTHREADED STUD 6
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 3
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRPULTIMATE TRIP TIME PER POLE IN SECONDSALL LOCATIONS NOMINAL 300.000
CPRQRESET METHODMANUAL
ADATBODY WIDTHINCHES MINIMUM 2.263 AND INCHES MAXIMUM 2.283
CPRXACTUATOR POSITION DESIGNATIONAT EACH POLE
CPRYEXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED
CPSMINTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
CQJXNOMINAL THREAD SIZEINCHES 0.138
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS NOMINAL AT 200 PCT 80.000 AND NOMINAL AT 300 PCT 25.000
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
CPRJTRIP RELEASE METHODALL LOCATIONS MAGNETIC-HYDRAULIC
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 200.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 1500.0
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
CMLPTHREAD QUANTITY PER INCH32
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 12.0
AKPXPOLE QUANTITY3
APNQARC QUENCHING METHODAIR
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 6
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES MINIMUM 1.990 AND INCHES MAXIMUM 2.010
AFJNFRAGILITY FACTORMODERATELY RUGGED

Supersedes

This item replaces cancelled NIIN 005036419. An older drawing citing one of those numbers resolves here.