Home / MS parts / NSN 5925-00-513-7610
NSN 5925-00-513-7610  ·  NIIN 005137610  ·  FSC 5925
NO DASHES 5925005137610
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

38 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
ADAQBODY LENGTHINCHES NOMINAL 5.000
CPRZAUXILIARY SWITCH FUNCTION AND QUANTITYALARM 1
AAQLBODY STYLE
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS INSTANTANEOUS AND TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT138.0
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
ADATBODY WIDTHINCHES NOMINAL 4.750
ADAUBODY HEIGHTINCHES NOMINAL 4.625
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 3.625
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 1.688
AEBVUNTHREADED MOUNTING HOLE DIAMETERINCHES NOMINAL 0.250
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES NOMINAL 4.500
AEGJSWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONAT POLE TWO
AJECBOSS HEIGHTINCHES NOMINAL 0.312
AKPXPOLE QUANTITY3
AXHRMOUNTING FACILITY TYPE AND QUANTITYUNTHREADED HOLE(S) 2
TTQYTERMINAL TYPE AND QUANTITYQUICK DISCONNECT, FEMALE 6
CQSMSWITCH LOCATION AND POSITION DESIGNATIONINTERNAL AT POLE TWO
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 10.000 AND MAXIMUM AT 200 PCT 180.000
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT
CRCFTRIP RELEASE AMBIENT TEMP RATINGALL LOCATIONS CELSIUS NOMINAL 50.0
CRTKSWITCH TERMINAL TYPESCREW
CSSXSWITCH CURRENT RATING AND TYPE IN AMPSAC 10.0 AND DC 10.0
CSWPSWITCH VOLTAGE RATING AND TYPE IN VOLTSAC 125.0 AND DC 125.0
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 25.0 AND AMPERES DC 25.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 125.0 AND DC 125.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 10000.0 AND DC 5000.0
FREQFREQUENCY IN HERTZ60.0
AEHADISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES NOMINAL 1.500
CPRJTRIP RELEASE METHODALL LOCATIONS THERMAL-MAGNETIC
CTJSUNPACKAGED UNIT WEIGHTPOUNDS NOMINAL 5.500
MATTMATERIALCASE PLASTIC