Home / MS parts / NSN 5925-00-620-5844
NSN 5925-00-620-5844  ·  NIIN 006205844  ·  FSC 5925
NO DASHES 5925006205844
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

43 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
CPRYEXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED
CSSXSWITCH CURRENT RATING AND TYPE IN AMPSAC 10.0 AND DC 10.0
CSWPSWITCH VOLTAGE RATING AND TYPE IN VOLTSAC 125.0 AND DC 125.0
CRCFTRIP RELEASE AMBIENT TEMP RATINGALL LOCATIONS CELSIUS NOMINAL 50.0
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
AJECBOSS HEIGHTINCHES NOMINAL 0.312
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES NOMINAL 4.625
AKPXPOLE QUANTITY3
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONAT POLE TWO
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 10.000 AND MAXIMUM AT 200 PCT 210.000
CRTKSWITCH TERMINAL TYPETAB, SOLDER LUG
CPRZAUXILIARY SWITCH FUNCTION AND QUANTITYALARM 1
CQJXNOMINAL THREAD SIZEINCHES 0.250
CQSMSWITCH LOCATION AND POSITION DESIGNATIONEXTERNAL AT POLE TWO
TESTTEST DATA DOCUMENTSPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.). 81349--IL-C-17588
THSDTHREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
TTQYTERMINAL TYPE AND QUANTITYTHREADED STUD 6
ZZZKSPECIFICATION/STANDARD DATAGOVERNMENT SPECIFICATION 81349--IL-C-17588
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 150.0 AND AMPERES DC 150.0
ADATBODY WIDTHINCHES NOMINAL 4.750
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES NOMINAL 4.250
FREQFREQUENCY IN HERTZ60.0
MATTMATERIALCASE PLASTIC
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 125.0 AND DC 125.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 10000.0 AND DC 5000.0
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
CPRJTRIP RELEASE METHODALL LOCATIONS THERMAL-MAGNETIC
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS INSTANTANEOUS AND TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT138.0
CPRPULTIMATE TRIP TIME PER POLE IN SECONDSALL LOCATIONS NOMINAL 3600.000
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 3.625
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 1.688
CMLPTHREAD QUANTITY PER INCH20
AEGJSWITCH CONTACT ARRANGEMENTSINGLE POLE, SINGLE THROW, NORMALLY CLOSED
AEHADISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES NOMINAL 0.750
ADAQBODY LENGTHINCHES NOMINAL 5.000
AAQLBODY STYLE
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 2
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT