34 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES MAXIMUM 1.700
AKPXPOLE QUANTITY1
AFJNFRAGILITY FACTORMODERATELY RUGGED
CPRXACTUATOR POSITION DESIGNATIONAT POLE ONE
CPSMINTERNAL TRIP RELEASE CONFIGURATIONSINGLE LOCATION SERIES TRIP
CQJXNOMINAL THREAD SIZEINCHES 0.375
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTSINGLE LOCATION MINIMUM AT 200 PCT 0.055 AND MAXIMUM AT 200 PCT 0.950
AAJETHREAD PITCH DIAMETERSINCHES 0.3503 TO 0.3537
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
CPRWACTUATOR FUNCTIONTRIP-RESET
ADAQBODY LENGTHINCHES MAXIMUM 1.562
ADATBODY WIDTHINCHES MAXIMUM 0.625
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES MAXIMUM 0.906
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND MOISTURE RESISTANT AND SALT SPRAY PROOF AND HERMETICALLY SEALED
CTJSUNPACKAGED UNIT WEIGHTGRAMS NOMINAL 50.0
FREQFREQUENCY IN HERTZ60.0
THSDTHREAD SERIES DESIGNATORUNEF
TTQYTERMINAL TYPE AND QUANTITYWIRE HOOK 2
BBRJSPECIAL HANDLING FEATUREMAGNETIC
CMLPTHREAD QUANTITY PER INCH32
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLESINGLE LOCATION AMPERES AC 8.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSSINGLE LOCATION AC 230.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSSINGLE LOCATION AC 1000.0
CPRHCIRCUIT PROTECTION TYPESINGLE LOCATION OVERCURRENT
CPRJTRIP RELEASE METHODSINGLE LOCATION MAGNETIC
APNQARC QUENCHING METHODAIR
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED BUSHING WITH PANEL SEAL 1
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
AAQLBODY STYLE
CPRLTRIP RELEASE CHARACTERISTICSINGLE LOCATION TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT115.0
CPRQRESET METHODMANUAL
ABXDBUSHING LENGTHINCHES MINIMUM 0.332 AND INCHES MAXIMUM 0.380