Home / MS parts / NSN 5925-01-323-5784
NSN 5925-01-323-5784  ·  NIIN 013235784  ·  FSC 5925
NO DASHES 5925013235784
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

41 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
AAJETHREAD PITCH DIAMETERSINCHES 0.1177 TO 0.1214
AAQLBODY STYLE
ADAQBODY LENGTHINCHES MAXIMUM 2.530
ADATBODY WIDTHINCHES MAXIMUM 2.280
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES MINIMUM 1.924 AND INCHES MAXIMUM 1.952
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES MINIMUM 0.740 AND INCHES MAXIMUM 0.760
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES MINIMUM 2.050 AND INCHES MAXIMUM 2.070
AEHADISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTHINCHES MINIMUM 0.740 AND INCHES MAXIMUM 0.760
AFJNFRAGILITY FACTORMODERATELY RUGGED
AJECBOSS HEIGHTINCHES MAXIMUM 0.155
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES MINIMUM 2.415 AND INCHES MAXIMUM 2.535
AKPXPOLE QUANTITY3
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 6
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
CMLPTHREAD QUANTITY PER INCH32
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLESECOND LOCATION AMPERES AC 25.0
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEFIRST LOCATION AMPERES AC 5.0
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLETHIRD LOCATION AMPERES AC 25.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 250.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 1000.0
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
CPRJTRIP RELEASE METHODALL LOCATIONS MAGNETIC-HYDRAULIC
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT115.0
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 3
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONAT EACH POLE
CPRYEXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED
CPSMINTERNAL TRIP RELEASE CONFIGURATIONALL LOCATIONS SERIES TRIP
CQJXNOMINAL THREAD SIZEINCHES 0.138
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTFIRST LOCATION MINIMUM AT 200 PCT 20.000 AND MAXIMUM AT 200 PCT 80.000
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTTHIRD LOCATION MINIMUM AT 200 PCT 0.200 AND MAXIMUM AT 200 PCT 0.800
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTSECOND LOCATION MINIMUM AT 200 PCT 0.200 AND MAXIMUM AT 200 PCT 0.800
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDDUSTPROOF AND FUNGUS PROOF
FREQFREQUENCY IN HERTZ400.0
MATTMATERIALCASE PLASTIC
THSDTHREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
TTQYTERMINAL TYPE AND QUANTITYTHREADED STUD 6