MODULE,LOAD SENSING
Generators and Generator Sets, Electrical
Technical characteristics
1 row
Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.
| MRC | Requirement | Value |
|---|---|---|
| TEXT | GENERAL CHARACTERISTICS ITEM DESCRIPTION | 27V NOM,1.0 AMP MAX INPUT,SENSING SIGNAL V3 PHASE,4 WIRE AC SIGNAL,SIGNAL NOT TO EXCEED 16V RMS,TRIP POINT POWER TO CONTACTS 2 AND 3 DISENGAGED WHEN CURRENT IN ANY PHASE HAS RISEN TO 125 NOM LOAD BANK CAPACITY,TRIP TIME LESS THAN 50 M SEC,50-400 HZ FREQUENCY,M65DEG TO 125 DEG F,INDUCTIVE OR RESISTIVE LOAD,CONNECTIONS 6AND 8 MODE AUTO-POWER TO LOAD IS CONTROLLED BY SENSING SIGNAL,CLOSED-MANUAL-SENSING CONTROL DEACTIVATED,CONNECTIONS 2AND 3 AC INPUT APPEARS FULL WAVE RECTIFIED BETWEEN CONTACTSPROVIDED SENSING SIGNAL IS NOT AT OR ABOVE TRIP POINT OR MODE IS MANUAL,CONNECTIONS 3 AND 9 MOMENTARY CLOSE RESETS POWER TO LOAD,CONNECTIONS 1 AND 3 MUST BE CLOSED FOR SENSING CONTROL,CONNECTIONS 10,11 AND 12 3 PHASE SENSING SIGNAL CONNECTION,TERMINAL 8 IS COMMON,CONNECTIONS 4 AND 5 AC INPUT POWER |