Technical characteristics from the federal item record
MRCRequirementValue
FREQFREQUENCY IN HERTZ60.0
MATTMATERIALCASE PLASTIC
CRCFTRIP RELEASE AMBIENT TEMP RATINGALL LOCATIONS CELSIUS NOMINAL 40.0
CTJSUNPACKAGED UNIT WEIGHTPOUNDS NOMINAL 3.000
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTALL LOCATIONS MINIMUM AT 200 PCT 30.000 AND MAXIMUM AT 200 PCT 85.000
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDDUSTPROOF AND GENERAL PURPOSE AND FUNGUS RESISTANT
CPRXACTUATOR POSITION DESIGNATIONAT POLE TWO
CPRQRESET METHODMANUAL
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
CPRWACTUATOR FUNCTIONTRIP-RESET
AAQLBODY STYLE
ABXDBUSHING LENGTHINCHES NOMINAL 0.125
ADAQBODY LENGTHINCHES NOMINAL 6.000
ADATBODY WIDTHINCHES NOMINAL 2.750
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 5.062
AEBQCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTHINCHES NOMINAL 1.375
AEBVUNTHREADED MOUNTING HOLE DIAMETERINCHES NOMINAL 0.188
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES NOMINAL 4.500
AFJNFRAGILITY FACTORMODERATELY RUGGED
TTQYTERMINAL TYPE AND QUANTITYCOMPRESSION 4
CPRHCIRCUIT PROTECTION TYPEALL LOCATIONS OVERCURRENT
CPRJTRIP RELEASE METHODALL LOCATIONS THERMAL-MAGNETIC
CPRLTRIP RELEASE CHARACTERISTICALL LOCATIONS TIME DELAY
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSALL LOCATIONS AC 240.0 AND DC 250.0
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES NOMINAL 3.375
AKPXPOLE QUANTITY2
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
AXHRMOUNTING FACILITY TYPE AND QUANTITYUNTHREADED HOLE(S) 2
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
BBRJSPECIAL HANDLING FEATUREMAGNETIC
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLEALL LOCATIONS AMPERES AC 25.0 AND AMPERES DC 25.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSALL LOCATIONS AC 10000.0 AND DC 5000.0

Supersedes