TRANSFORMER,POWER
Transformers: Distribution and Power Station
Technical characteristics
4 rows
Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.
| MRC | Requirement | Value |
|---|---|---|
| FEAT | SPECIAL FEATURES | OVERHEAD DSITRIBUTION TRANSFORMER; S - CONVENTIONAL; 25 KVA; NO LOAD - 60 WATTS AT 85 DEGREES CELSIUS; LOAD - 311 WATTS AT 85 DEGREES CELSIUS; TOTAL LOSS - 371 WATTS 2400/4160Y HV; 60 BIL; ALUMINUM HV WINDING MATERIAL WITH TAPS AT 2520, 2460, 2340, 2280 227/480Y LV; 30 BIL; NON-LV ITERLACED; ALUMINUM LV WINDING MATRIAL; 60 HERTZ (HZ); 1 PHASE; DEPTH 26.00 INCH; LENGTH 30 INCH; 65 TEMPERATURE RISE; 1 HV TC, ABB, EXT (LEVER) SETSCREW LOCKABLE HANDLE, 5 POS, NO./LTR; 1 HV LINE BUSHING, 75KV BILL, 8 INCH CREEP, 8-2 SIZE 3-HOLE SPINTOP, WALL MOUNT; 2 LV BUSH-EYEBOLT FOR NUMBER 6 - NUMBER 4/0, CM SPEED MOUNTING, .38 STUD; 15 GALLONS OF TRANSFORMER OIL; 1 - 17.5 INCH CARBON STIL COVER, NO HV BUSHING HOLE; WEIGHT 369.04 POUNDS |
| ADAU | BODY HEIGHT | INCHES NOMINAL 28.00 |
| CXCY | PART NAME ASSIGNED BY CONTROLLING AGENCY | TRANSFORMER |
| ADAT | BODY WIDTH | INCHES NOMINAL 26.00 |