Home / MS parts / NSN 5925-00-728-9615
NSN 5925-00-728-9615  ·  NIIN 007289615  ·  FSC 5925
NO DASHES 5925007289615
In Stock

CIRCUIT BREAKER

Circuit Breakers

Technical characteristics

34 rows

Straight from the federal item record. Entries the record leaves empty are shown empty — nothing is filled in on its behalf.

Technical characteristics from the federal item record
MRCRequirementValue
AAQLBODY STYLE
ADAQBODY LENGTHINCHES NOMINAL 2.500
AJWXMOUNTING SURFACE TO TERMINAL END DISTANCEINCHES NOMINAL 2.611
CQJXNOMINAL THREAD SIZEINCHES 0.138
CQWNTRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENTSINGLE LOCATION MINIMUM AT 200 PCT 0.250 AND MAXIMUM AT 200 PCT 0.900
CMLPTHREAD QUANTITY PER INCH32
AEBYDISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTHINCHES NOMINAL 2.062
AFJNFRAGILITY FACTORMODERATELY RUGGED
AJECBOSS HEIGHTINCHES NOMINAL 0.140
MATTMATERIALCASE PLASTIC
THSDTHREAD SERIES DESIGNATORUNIFIED NATIONAL COARSE (UNC)
AKPXPOLE QUANTITY1
APNQARC QUENCHING METHODMAGNETIC BLOWOUT
AXHRMOUNTING FACILITY TYPE AND QUANTITYTHREADED HOLE(S) 2
BBRGSTORAGE TYPEGENERAL PURPOSE WAREHOUSE
BBRJSPECIAL HANDLING FEATUREMAGNETIC
CPLMMAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLESINGLE LOCATION AMPERES AC 25.0
CPRFOPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTSSINGLE LOCATION AC 250.0
CPRGMAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPSSINGLE LOCATION AC 1000.0
CPRHCIRCUIT PROTECTION TYPESINGLE LOCATION OVERCURRENT
CPRJTRIP RELEASE METHODSINGLE LOCATION MAGNETIC-HYDRAULIC
CPRLTRIP RELEASE CHARACTERISTICSINGLE LOCATION TIME DELAY
CPRRMAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
CPRTMANUAL ACTUATOR TYPE AND QUANTITYTOGGLE 1
CPRWACTUATOR FUNCTIONTRIP-RESET
CPRXACTUATOR POSITION DESIGNATIONAT POLE ONE
CPSMINTERNAL TRIP RELEASE CONFIGURATIONSINGLE LOCATION SERIES TRIP
ADATBODY WIDTHINCHES NOMINAL 0.750
CPRNULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0
CPRQRESET METHODMANUAL
FREQFREQUENCY IN HERTZ50.0 OR 60.0
TTQYTERMINAL TYPE AND QUANTITYTHREADED STUD 2
CQXFINCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDDUSTPROOF AND FUNGUS PROOF
AEBPCENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTHINCHES NOMINAL 1.938